DEFINITY Enterprise Communications Server  Release 6
Maintenance for R6vs/si  
555-230-127   
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-1289
TBRI-PT (TN2185 ISDN Trunk-Side BRI Port) 
10
BRI Port Local LAN Looparound Test (#618)
This test is destructive
.
This test checks the connectivity of the BRI port across the LAN bus. Because 
this test is destructive, run this test only if the port is out-of-service.
Failures of this test indicate either on-board faults associated with theTBRI-PT 
hardware on the circuit pack or problems with the LAN Bus, which is used to 
form connectivity between the switch and the TBRI-PT.
If the port is in a state other than out-of-service, the BRI Port Local LAN 
Looparound Test will abort. If the port is out-of-service, then the port is put into a 
local looparound mode and the following test is executed.
1004
ABORT
The port has been seized by a user for a valid call. Use the 
status bri-port
 
command to determine when the port is available for testing.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to abort and the port is not in use, escalate the 
problem.
1005
ABORT
This test is not valid for this type of translation. Ports administered as 
“ASAI” or “ADJK” can not run this test, because the B channels associated 
with the port are not used by ASAI or AT&T Adjunct Links. This is a normal 
condition.
2012
ABORT
Internal system error
2100
ABORT
Could not allocate the necessary resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1, 2
FAIL
The NPE of the tested port was found to be transmitting in error, causing 
noisy and unreliable connections. Error code 1 indicates that the NPE 
Crosstalk Test failed on Channel B1. Error code 2 indicates that the NPE 
Crosstalk Test failed on Channel B2.
1. Replace circuit pack.
PASS
The port is correctly using its allocated time slots.
1. To be sure that this is not an intermittent problem, repeat this test a 
maximum of 10 times to ensure it continues to pass.
2. If complaints still exist, examine the connections and wiring.
Table 10-443.
TEST #617 NPE Crosstalk Test  — 
Continued
Error 
Code
Test 
Result
Description/ Recommendation
Continued on next page