555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-175
BRI-PORT (ISDN-BRI Port), ABRI-PORT (ASAI ISDN-BRI Port)
10
not indicate a problem with the ISDN-BRI circuit pack. This test is useful for
verifying the repair of the problem.
verifying the repair of the problem.
Receive FIFO Overflow Error Counter Test (#625)
This test reads and clears the BRI port’s Receive FIFO Overflow error counter
maintained on the BRI-LINE circuit pack. This counter is incremented by the
circuit pack when it detects an overflow of its receive buffers. The test passes if
the value of the counter is 0 (that is, the error is cleared). If the counter is
non-zero, the test fails, and the value of the counter is displayed in the Error
Code field.
maintained on the BRI-LINE circuit pack. This counter is incremented by the
circuit pack when it detects an overflow of its receive buffers. The test passes if
the value of the counter is 0 (that is, the error is cleared). If the counter is
non-zero, the test fails, and the value of the counter is displayed in the Error
Code field.
Table 10-62.
TEST #624 Layer 1 Transmission Error Counter Test
Error
Code
Code
Test
Result
Description/ Recommendation
2000
ABORT
Response to the test was not received from the circuit pack within the
allowable time period.
allowable time period.
1. If the test aborts repeatedly a maximum of five times, reset the
circuit pack via the
busyout board PCSS
and
reset board PCSS
commands.
2. If the test aborts again, replace the circuit pack.
2012
ABORT
Internal System Error.
2100
ABORT
Could not allocate necessary system resources to run test.
1. Retry the command at one-minute intervals a maximum of five
times.
2. If the test continues to fail, escalate the problem.
value
FAIL
The BRI-LINE circuit pack is still detecting errors of this type. The Error
Code field contains the value of this counter.
Code field contains the value of this counter.
1. Retry the command at one-minute intervals a maximum of five
times.
2. If the test continues to fail, review the results of other tests in the
Long Test Sequence. Pay particular attention to the results of the
Level 1 Status Inquiry test. Follow repair procedures for any of the
executed tests if they fail. Otherwise, go to the next step.
Level 1 Status Inquiry test. Follow repair procedures for any of the
executed tests if they fail. Otherwise, go to the next step.
3. If the tests for the endpoints or adjunct pass and the Layer 1
Transmission Error Counter Test continues to fail, check the wiring
to the endpoints or adjunct. If the wiring appears to be fine,
escalate the problem.
to the endpoints or adjunct. If the wiring appears to be fine,
escalate the problem.
PASS
The Layer 1 Transmission error counter was read correctly and has a
value of 0.
value of 0.
Continued on next page