Check first when you have a trouble
5
5.5.8
Speed varies during operation
5.5.9
Operation mode is not changed properly
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Load 
Load varies during an operation. (V/F Control)
Select Simple magnetic flux vector control
Input 
signal
Frequency setting signal is varying.
Check the frequency setting signal.
The frequency setting signal is affected by EMI.
Set filter to the analog input terminal using Pr. 74 Input 
filter time constant
Take countermeasures against EMI, such as using 
shielded wires for input signal lines.
Malfunction is occurring due to the undesirable current 
generated when the transistor output unit is connected.
Use terminal PC (terminal SD when source logic)  as a 
common terminal to prevent a malfunction caused by 
undesirable current.
Multi-speed command signal is chattering.
Take countermeasures to suppress chattering.
Parameter 
Setting
Fluctuation of power supply voltage is too large.
Change the Pr. 19 Base frequency voltage setting (about 
3%) under V/F control.
Pr. 80 Motor capacity setting is improper for the 
capacities of the inverter and the motor for Simple 
magnetic flux vector control.
Check the Pr. 80 Motor capacity setting.
Wiring length is too long for V/F control, and a voltage 
drop occurs.
Adjust Pr. 0 Torque boost by increasing with 0.5% 
increments for low-speed operation.
Change to Simple magnetic flux vector control.
Hunting occurs by the generated vibration, for example, 
when structural rigidity at load side is insufficient.
Disable automatic control functions, such as energy 
saving operation, fast-response current limit function, 
regeneration avoidance function, Simple magnetic flux 
vector control and stall prevention.
For PID control, set smaller values to Pr.129 PID 
proportional band
 and Pr.130 PID integral time.
Adjust so that the control gain decreases and the level of 
safety increases. 
Change Pr. 72 PWM frequency selection setting.
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Input 
signal
Start signal (STF or STR) is ON.
Check that the STF and STR signals are OFF.
When either is ON, the operation mode cannot be 
changed.
Parameter 
Setting
Pr. 79 setting is improper.
When Pr. 79 Operation mode selection setting is "0" (initial 
value), the inverter is placed in the External operation 
mode at input power ON. To switch to the PU operation 
mode, press 
 on the operation panel (press 
 
when the parameter unit (FR-PU04/FR-PU07) is used) . 
At other settings (1 to 4, 6, 7), the operation mode is 
limited accordingly.
Operation mode and a writing device do not 
correspond.
Check Pr. 79, Pr. 338, Pr. 339, Pr. 550, Pr. 551, and select 
an operation mode suitable for the purpose. 
195,