Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
352
Check first when you have a trouble
5.5.10 Operation panel (FR-DU07) display is not operating
5.5.11 Motor current is too large
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Main 
Circuit,
Control 
Circuit
Power is not input.
Input the power.
Front 
cover
Operation panel is not properly connected to the 
inverter.
Check if the inverter front cover is installed securely.
The inverter cover may not fit properly when using wires 
whose size are 1.25mm
2
 or larger, or when using many 
wires, and this could cause a contact fault of the 
operation panel.
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Parameter 
Setting
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F 
control, so the stall prevention function is activated. 
Increase/decrease Pr. 0 Torque boost setting value by 
0.5% increments to the setting.
V/F pattern is improper.
(Pr. 3, Pr. 14, Pr. 19)
Set rated frequency of the motor to Pr. 3 Base frequency.
Use Pr. 19 Base frequency voltage to set the base voltage 
(e.g. rated motor voltage).
Change Pr. 14 Load pattern selection according to the load 
characteristic. (V/F control)
Stall prevention function is activated due to a heavy 
load.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level  higher according 
to the load. (Setting Pr. 22 too large may result in 
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.