Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
353
Check first when you have a trouble
5
5.5.12 Speed does not accelerate
5.5.13 Unable to write parameter setting
5.5.14 Power lamp is not lit
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Input 
signal
Start command and frequency command are chattering.
Check if the start command and the frequency 
command are correct.
The wiring length used for analog frequency command 
is too long, and it is causing a voltage (current) drop.
Perform analog input bias/gain calibration.
Input signal lines are affected by external EMI.
Take countermeasures against EMI, such as using 
shielded wires for input signal lines.
Parameter 
Setting
Pr. 1, Pr. 2, Pr. 18, calibration parameter C2 to C7 settings 
are improper.
Check the settings of Pr. 1 Maximum frequency and Pr. 2 
Minimum frequency
. If you want to run the motor at 120Hz 
or higher, set Pr. 18 High speed maximum frequency.
Check the calibration parameter C2 to C7 settings.
The maximum voltage (current) input value is not set 
during the external operation. (Pr.125, Pr.126, Pr.18)
Check the Pr.125 Terminal 2 frequency setting gain 
frequency
 and Pr.126 Terminal 4 frequency setting gain 
frequency
 settings.
To operate at 120Hz or higher, set Pr.18 High speed 
maximum frequency
.
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F 
control, so the stall prevention function is activated. 
Increase/decrease Pr. 0 Torque boost setting value by 
0.5% increments so that stall prevention does not occur.
V/F pattern is improper.
(Pr. 3, Pr. 14, Pr. 19)
Set rated frequency of the motor to Pr. 3 Base frequency.
Use Pr. 19 Base frequency voltage  to set the base voltage 
(e.g. rated motor voltage).
Change Pr. 14 Load pattern selection according to the load 
characteristic.  (V/F control)
Stall prevention function is activated due to a heavy 
load.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level  higher according 
to the load. (Setting Pr. 22 too large may result in 
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
During PID control, output frequency is automatically controlled to make measured value = set point.
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Input 
signal
Operation is being performed (signal STF or STR is 
ON).
Stop the operation.
When Pr. 77 = "0" (initial value), write is enabled only 
during a stop.
Parameter 
Setting
You are attempting to set the parameter in the External 
operation mode.
Choose the PU operation mode.
Or, set Pr. 77 = "2" to enable parameter write regardless 
of the operation mode. 
Parameter is disabled by the Pr. 77 Parameter write 
selection
 setting.
Check Pr. 77 Parameter write selection setting.
Key lock is activated by the Pr. 161 Frequency setting/key 
lock operation selection
 setting.
Check Pr. 161 Frequency setting/key lock operation selection 
setting.
Operation mode and a writing device do not 
correspond.
Check Pr. 79, Pr. 338, Pr. 339, Pr. 550, Pr. 551, and select 
an operation mode suitable for the purpose. 
195, 
Check
points
Possible Cause
Countermeasures
Refer 
to 
page
Main 
Circuit,
Control 
Circuit
Wiring or installation is improper.
Check for the wiring and the installation.
Power lamp is lit when power supply is input to the 
control circuit (R1/L11, S1/L21).