Adjustment, if required, is performed as follows:
1.  Set  primary  system  temperature  control  dial  (thermostat)  at 
lowest setting so that boiler will not call for heat.
2.  Attach  a  pressure  gauge  to  the  tapping  in  the  control  string 
elbow.
3.  Reset primary system temperature control dial (thermostat) to 
highest setting.  Main burner will now ignite.
4.  With main burner firing, adjust pressure, if necessary, by turning 
pressure regulator adjusting screw with a screwdriver.
 
 •  Clockwise to increase pressure.
 
 
 •  Counterclockwise to decrease pressure.
5.  Set  primary  system  temperature  control  dial  (thermostat)  to 
lowest setting.
6.  Remove pressure gauge and replace sealing plug.
7.  Set  primary  system  temperature  control  dial  (thermostat)  to 
desired setting.
  WARNING
DO NOT INCREASE GAS PRESSURE ABOVE THAT SPECIFIED 
ON THE RATING PLATE, AS OVERFIRING WILL RESULT IN 
DAMAGE TO THE BOILER, AS WELL AS INCREASED RISK 
OF FIRE, SOOTING AND ASPHYXIATION.
If gas pressure regulator cannot be adjusted to correct pressure with 
sufficient gas pressure at the valve, replace with new gas valve.
WIRING
WIRING CONNECTIONS
  CAUTION
LABEL  ALL  WIRES  PRIOR  TO  DISCONNECTION  WHEN 
SERVICING  CONTROLS.  WIRING  ERRORS  CAN  CAUSE 
IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER 
OPERATION AFTER SERVICING.
1.  CONVENTIONAL INSTALLATIONS
ALL ELECTRICAL WORK MUST BE INSTALLED IN ACCORDANCE 
WITH  NATIONAL  ELECTRICAL  CODE, ANSI/NFPA  70 AND/
OR THE CANADIAN ELECTRICAL CODE, PART 1, CSA C22.1, 
ELECTRICAL  CODE  AND  MUST  CONFORM  TO  LOCAL 
REGULATIONS.
The boiler, when installed, must be electrically bonded to ground in 
accordance with the requirements of the authority having jurisdiction 
or, in the absence of such requirements, with the National Electrical 
Code, ANSI/NFPA 70 and/or the Canadian Electrical Code Part 1, 
CSA C22.1, Electrical Code.
STRICT ADHERENCE TO PIPING AND WIRING DIAGRAMS IS 
REQUIRED TO PREVENT CONSTANT PUMP OPERATION WHEN 
SYSTEM TEMPERATURE CONTROL IS SATISFIED. OTHERWISE 
THE  WARRANTY  IS  VOID AS  STIPULATED  IN  THE  LIMITED 
WARRANTY ON THE INSTRUCTIONS MANUAL.
The electrical connections must be made so that the circulator will 
operate before the gas valve opens. At no time may the controlling 
system allow the burner to fire when there is no water flow through 
the boilers.
Refer  to  the  diagrams  in  Figures  16  and  17  on  pages  24  and 
25  for  proper  wiring  sequence  with  conventional  single  boiler 
installations.
The  THERMAL  BALANCER  shown  is  factory  included  by  
A. O. Smith. This device serves as a pump shutdown delay switch to 
balance the rising boiler water temperature to system temperature 
before  the  pump  stops.  Overshooting  of  boiler  temperature  is 
prevented and stack loss after shutdown is negligible.
 WARNING
AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF 
ELECTRIC SHOCK OR POSSIBLE ELECTROCUTION. Make the 
ground  connection  to the  screw provided  in  the  electrical  supply 
junction box on the boiler.
IF ANY  OF  THE  ORIGINAL  WIRE, AS  SUPPLIED  WITH  THE 
APPLIANCE,  MUST  BE  REPLACED,  IT  MUST  BE  REPLACED 
WITH TYPE 105
0
C WIRE OR ITS EQUIVALENT, EXCEPT FOR 
THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250
0
AND WIRES CONNECTED TO THE COIL PROTECTOR WHICH 
ARE 200
0
C.