•  In table 7 on page 21, select the row showing the distance to 
the most remote outlet or the next longer distance if the table 
does not give the exact length. This is the only distance used in 
determining the size of any section of gas piping. If the gravity 
factor is to be applied, the values in the selected row of table 7 
are multiplied by the appropriate multiplier from table 8.
•  Total the gas demands of all appliances on the piping system.  
Enter table 7, on the left hand side, at the row equal to or just 
exceeding the distance to the most remote outlet. Select the 
pipe size in the row with a capacity equal to or just exceeding 
the total gas demand. This is the required main gas supply line 
size leading away from the gas meter or regulator. To determine 
the pipe size required for each branch outlet leading away from 
the main supply line, determine the gas demand for that outlet. 
Enter  table  7  on  the  same  row,  and  select  the  branch  pipe 
size for a capacity equal to or just exceeding the demand at 
that outlet. The main line can be resized for a lesser capacity 
after  each  branch  outlet,  since  the  gas  demand  is  reduced. 
Total the gas demands of all remaining appliances branching 
off downstream on the main gas line. Re-enter table 8 in the 
same row and select the appropriate pipe size with adequate 
capacity. Repeat the branch sizing and main line re-sizing for 
any remaining appliances in the system.
EXAMPLE
Job Condition:
Determining the required gas pipe size for a system composed of two 
HW-420 boilers and two HW-610 boilers to be installed as a multiple 
group, 50 lineal feet from meter. Gas to be used has a .60 specific 
gravity and heating value of 1,000 Btu per cubic foot.
Solution:
2 HW-420 Boilers 
840,000 Btuh
2 HW-610 Boilers 
1,220,000 Btuh
Total Btuh Input 
2,060,000 Btuh
Total Btuh Input 
2,060,000 Btuh  =   2,060 cf/h
Btu per Cubic Foot of Gas            1,000      
With  a  cubic  foot  per  hour  demand  of  2,060  and  with  50  lineal 
feet  of  gas  supply  line,  table  7  shows  a  pipe  size  of  3"  (76mm)  
is required.
NOTE:  For other than .60 specific gravity, apply multiplier factor as 
shown in table 8.
TABLE 8.
MULTIPLIERS TO BE USED WITH TABLE 7 WHEN APPLYING 
THE GRAVITY FACTOR TO OTHER THAN .60 SPECIFIC GRAVITY
Specific
Gravity
Multiplier
Specific
Gravity
Multiplier
.35
1.31
1.00
.78
.40
1.23
1.10
.74
.45
1.16
1.20
.71
.50
1.10
1.30
.68
.55
1.04
1.40
.66
*.60 (Nat.)
1.00
*1.50 (Prop.)
.63
.65
.96
1.60
.61
.70
.93
1.70
.59
.75
.90
1.80
.58
.80
.87
1.90
.56
.85
.84
*2.00 (Butane)
.55
.90
.82
2.10
.54
*Use these correction factors if exact specific gravity of the gas is not known.
GAS PRESSURE REGULATORS
The gas pressure regulator is included in the combination gas valve, 
Figure 15, and is set to operate on the gas specified on the boiler 
model and rating plate.
GROUND
TERMINALS (2)
PILOT
OUTLET
GAS
CONTROL
PILOT ADJUSTMENT
(UNDER CAP SCREW)
PILOT SUPPLY
OUTLET
INLET
GAS VALVE KNOB
PRESSURE REGULATOR
ADJUSTMENT
PILOT ADJUSTMENT
UNDER SCREW
FIGURE 15.
Periodically check main burner, Figure 34 on page 39, and pilot 
flame, Figure 35 on page 40, for proper operation.  This should 
be checked every six months.
Do not subject the gas valve to inlet gas pressures of more than 14" 
W.C. (1/2 P.S.I.).  If higher gas pressures are encountered, a service 
regulator is necessary.
TABLE 9.
CORRECT MANIFOLD PRESSURE FOR FULL
BOILER INPUT (IN INCHES OF WATER COLUMN)
Model
Number
Rated
Input
Manifold Pressure
Natural
Propane
HW-300
300,000
3.5
10.0
HW-399
399,000
3.2
9.5
HW-420
420,000
3.5
10.0
HW-520
520,000
3.5
10.0
HW-610
610,000
3.5
10.0
HW-670 Nat.
660,000
3.5
HW-670 Prop.
670,000
10.0