A.O. Smith HW 610 ユーザーズマニュアル

ページ / 56
21
Use  table  7,  or  CAN/CSA  B149.1  (current  edition)  to 
size  iron  pipe  or  equivalent  gas  supply  line.  Table  7  
is  based  on  a  pressure  drop  of  0.3  inches  of  water  and  
a  specific  gravity  of  0.60  approximately  that  of  natural  
gas. (LP gas has an S.G. of about 1.53). If the service pressure 
is five inches water column or less, use one pipe size larger in 
order to minimize pressure drop in the line.
TABLE 7.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER 
HOUR (BASED UPON A PRESSURE DROP OF 0.3 INCH 
WATER COLUMN AND 0.6 SPECIFIC GRAVITY GAS)
Distance 
from Gas 
Meter
Nominal Iron Pipe Size (Inches)
1/2
3/4
1
1 1/4 1 1/2
2
2 1/2
3
4
10 (3)
132 278 520 1,050 1,600 3,050 4,800 8,500 17,500
20 (6)
92
190 350 730 1,100 2,100 3,300 5,900 12,000
30 (9)
73
152 285 590
890 1,650 2,700 4,700 9,700
40(12)
63
130 245 500
760 1,450 2,300 4,100 8,300
50 (15)
56
115 215 440
670 1,270 2,000 3,600 7,400
60 (18)
50
105 195 400
610 1,150 1,850 3,250 6,800
70 (21)
46
96
180 370
560 1,050 1,700 3,000 6,200
80 (24)
43
90
170 350
530
990 1,600 2,800 5,800
90 (27)
40
84
160 320
490
930 1,500 2,600 5,400
100 (30)
38
79
150 305
460
870 1,400 2,500 5,100
125 (38)
34
72
130 275
410
780 1,250 2,200 4,500
150 (45)
31
64
120 250
380
710 1,130 2,000 4,100
175 (53)
28
59
110 225
350
650 1,050 1,850 3,800
200 (60)
26
55
100 210
320
610
980 1,700 3,500
*The heating value of Natural Gas is approximately 1,050 Btu/Ft
.3
.
Propane (LP) Gas has a heating value of approximately 2,500 Btu/Ft
3
.
1 cu. meter=35.31 cu. feet.
Where it is necessary to use more than the average number of pipe 
fittings i.e. elbows, tees, and valves in gas supply line, use a pipe 
larger than specified to compensate for increased pressure drop.
2B.  SIZING GAS SUPPLY LINE (For multiples of over three boilers of 
same size or for multiple installations of two or more mixed sizes).
Capacities  in  cubic  feet  per  hour  of  0.60  specific  gravity  gas  for 
different  sizes  and  lengths  are  shown  in  table  7.  No  additional 
allowance is necessary for an ordinary number of fittings.
Applications of the gravity factor converts the figures given in table 
7 to capacities with another gas of different specific gravity. Such 
application is accomplished by multiplying the capacities given in 
table 7 by the multipliers shown in table 8 on page 22.
To determine the size of each section of gas piping in a system within 
the range of table 7 proceed as follows:
•  Determine the gas demand of each appliance to be attached 
to the piping system. When table 7 is to be used to select the 
piping size, calculate the gas demand in terms of cubic feet 
per hour for each piping system outlet. The gas demand for 
an appliance can be found by dividing its heat input rate by 
the gas’s heating value.
•  Obtain or determine the length of piping from the gas meter or 
service regulator to the appliance(s).
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS 
SUPPLY  LINE,  A  DIRT  LEG  (SOMETIMES  CALLED  DRIP 
LEG  or  sediment  trap)  MUST  BE  INCORPORATED  IN  THE 
PIPING, see Figure 1 on page 6. The dirt leg must be readily 
accessible and not subject to freezing conditions. INSTALL IN 
ACCORDANCE  WITH  RECOMMENDATIONS  OF  SERVING 
GAS  SUPPLIERS.  (Refer  to  National  Fuel  Gas  Code,  ANSI 
Z223.1 or CAN/CSA-B 149.1 Installation Codes.                     
To  prevent  damage,  care  must  be  taken  not  to  apply  too 
much torque when attaching gas supply pipe to the gas valve  
gas inlet.
Fittings  and  unions  in  the  gas  line  must  be  the  metal  to  
metal type.
Apply joint compounds (pipe dope) sparingly and only to the 
male threads of pipe joints. Do not apply compound to the first 
two threads. Use compounds resistant to the action of liquefied 
petroleum gases.
THE BOILER AND ITS GAS CONNECTIONS MUST BE LEAK 
TESTED  BEFORE  PLACING  THE  BOILER  IN  OPERATION. 
Use soap and water solution or other material acceptable for 
the purpose in locating gas leaks. DO NOT USE MATCHES, 
CANDLES, FLAME OR OTHER SOURCES OF IGNITION FOR 
THIS PURPOSE.
DISCONNECT  THE  BOILER  AND  ITS  MAIN  MANUAL 
GAS  SHUTOFF  VALVE  FROM  THE  GAS  SUPPLY  PIPING  
SYSTEM DURING ANY PRESSURE TESTING OF THE GAS 
SUPPLY SYSTEM OVER 1/2 PSIG (3.5kPa). THE GAS SUPPLY 
LINE  MUST  BE  CAPPED  WHEN  NOT  CONNECTED  TO  
THE BOILER.
THE BOILER MUST BE ISOLATED FROM THE GAS SUPPLY 
PIPING  SYSTEM  BY  CLOSING  ITS  MAIN  MANUAL  GAS 
SHUTOFF  VALVE  DURING  ANY  PRESSURE  TESTING  OF 
THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES 
EQUAL TO OR LESS THAN 1/2 PSIG (3.5kPa).
PURGING AND SIZING
Gas line purging is required with new piping or systems in which 
air has entered.
 CAUTION
PURGING  SHOULD  BE  PERFORMED  BY  PERSONS 
EXPERIENCED IN THIS TYPE GAS SERVICE TO AVOID RISK OF 
FIRE OR EXPLOSION. PURGE DISCHARGE MUST NOT ENTER 
CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR. 
THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF 
IGNITION MUST BE INACTIVATED OR REMOVED.
1.  CORRECT GAS
Make sure the gas on which the boiler will operate is the same as 
that specified on the boiler rating plate. Do not install the boiler if 
equipped for a different type gas — consult your supplier.
2A.  SIZING  GAS  SUPPLY  LINE  (For  single  boiler  installations 
and  for  installations  of  multiples  of  two  or  three  of  same  
size boilers).