HIGH ALTITUDE INSTALLATIONS
IN CANADA
Acceptance of these models for use at altitudes above 2000 feet 
(600 m) is based on field test of the individual installation by the 
provincial/state authority having jurisdiction.
IN THE U.S.A.
 
WARNING
INSTALLATIONS ABOVE 2000 FEET REQUIRE REPLACEMENT 
OF  THE  BURNER  ORIFICES  IN ACCORDANCE  WITH  THE 
CURRENT  EDITION  OF  THE  NATIONAL  FUEL  GAS  CODE 
(ANSI  Z223.1).  FAILURE  TO  REPLACE  THE  ORIFICES  WILL 
RESULT IN IMPROPER AND INEFFICIENT OPERATION OF THE 
APPLIANCE RESULTING IN THE PRODUCTION OF INCREASED 
LEVELS OF CARBON MONOXIDE GAS IN EXCESS OF SAFE 
LIMITS  WHICH  COULD  RESULT  IN  SERIOUS  PERSONAL 
INJURY OR DEATH.
For  specific  orifice  requirements,  please  refer  to  the  appropriate 
section of the National Fuel Gas Code ANSI Z223.1.
You should contact your gas supplier for any specific changes which 
may be required in your area.
Ratings  specified  by  manufacturers  for  most  boilers  apply  for 
elevations up to 2000 feet (600 m).  For elevations above 2000 feet 
(600 m) ratings must be reduced by a rate of 4% for each 1000 feet 
(300 m) above sea level.
Example: If a boiler is rated at 610,000 Btu/hr. at sea level, to operate 
the boiler at 5000 feet (1500 m) it must be derated by 20% (4% x 5) 
to a new rating of 488,000 Btu/hr.
A. O. Smith does build some models specifically for high altitude 
service.  Please check the rating plate before making changes.
The input reduction is primarily achieved by reducing the size 
of the main burner orifices. To do this, the main burner orifices 
require  replacement  with  orifices  sized  for  the  particular 
installation elevation. When ordering, be sure to state the model 
number and the altitude of the location where the boiler is being 
installed.
Upon field deration of the boiler, adjustment to the gas pressure 
regulator  is  required.  See  CHECKING  AND  ADJUSTING 
THE  INPUT  in  this  manual  for  inlet  and  manifold  pressure 
requirements. Also, due to the input rating reduction required at 
high altitudes, the output rating of the appliance is also reduced 
and should be compensated for in the sizing of the equipment 
for applications.
AUTO RESET HIGH LIMIT
The  high  limit  is  a  safety  device  wired  in  series  with  the 
ignition system. Set the high limit control to approximately 10
0
F  
above  the  maximum  designed  system  temperature.  If  the  
boiler  outlet  water  temperature  should  exceed  the  high  
limit  setting,  the  main  gas  valve  will  close  but  the  circulator 
will continue to operate.  Maximum adjustable setting is 115
0
(239°F)  cut-out  with  a  3
0
C  (5
0
F)  to  25
0
C  (45
0
F)  adjustable 
differential, see Figure 2.
FIGURE 2.
INTERMITTENT IGNITION CONTROL MODULE
The  Honeywell  S-8600  control  module  contains  the  electronic 
components of the system and also serves as a control wiring system 
for the controls mounted on the heater. The control module performs 
the following functions:
1.  Checks for safe-start by sensing for a false flame condition on 
start-up.
2.  Generates a potential of 15,000 volts for spark ignition of the  
pilot burner.
3.  Opens the pilot valve.
4.  Discontinues ignition spark when the pilot flame is established. 
The  S-8600  control  used  on  propane  gas  models  provides 
safety lockout if the pilot fails to ignite within the pilot flame 
establishing  period.  The  S-8600  control  used  on  natural 
gas  models  continues  trial  for  ignition  until  pilot  flame  
is established.
5.  After proof of pilot flame, opens then main valve.
6.  On a power loss, shuts the heater down. When power is restored 
it will begin a new ignition cycle.
7.  On a loss of flame, shuts off main gas and starts trial for pilot ignition.
PLEASE  SEE  TROUBLESHOOTING  SECTION  FOR  MORE 
INFORMATION.
S-8600 INTERMITTENT IGNITION
CONTROL MODULE (IID)
FIGURE 3.
CONTROLS AND FUNCTION