A.O. Smith HW 610 ユーザーズマニュアル

ページ / 56
10
 
 
CAUTION
Paddle must be trimmed at the dotted arc. It must not touch the pipe or have any restriction when installed.
FIGURE 6.
To adjust the flow rate setting:
1.  Remove the flow switch cover.
2.  For higher flow rate - turn the range adjusting screw clockwise.
3.  For  lower  flow  rate  -  turn  the  range  adjusting  screw 
counterclockwise.
 
 
CAUTION
The switch is factory set at approximately the minimum flow rate, see 
Table 3 on page 9. It must not be set lower than the factory setting as 
this may result in the switch failing to return at 'no flow' condition.
4.  Replace flow switch cover. Where units are installed in multiples, 
each boiler must be individually protected by a safety flow switch.
SAFETY RELIEF VALVES
Your  local  code  authority  may  have  other  specific  relief  valve 
requirements not covered below.
  WARNING
THE  PURPOSE  OF A  SAFETY  RELIEF  VALVE  IS  TO AVOID 
EXCESSIVE PRESSURE OR TEMPERATURE INTO THE STEAM 
RANGE WHICH MAY CAUSE SCALDING AT FIXTURES, TANK 
EXPLOSION, SYSTEM OR BOILER DAMAGE.
TO AVOID SCALDING OR WATER DAMAGE A DRAIN LINE MUST 
BE CONNECTED TO A RELIEF VALVE TO DIRECT DISCHARGE 
TO A SAFE LOCATION.  A DRAIN LINE MUST NOT BE REDUCED 
FROM THE SIZE OF THE VALVE OUTLET AND IT MUST NOT 
CONTAIN ANY  VALVES  BETWEEN  THE  BOILER AND  THE 
RELIEF VALVE OR THE RELIEF VALVE AND THE DRAIN EXIT.  
IN ADDITION, THERE  SHOULD  NOT  BE ANY  RESTRICTIONS 
IN A  DRAIN  LINE  NOR  SHOULD  IT  BE  ROUTED  THROUGH 
AREAS WHERE FREEZING CONDITIONS MIGHT OCCUR.  DO 
NOT THREAD OR CAP THE DRAIN LINE EXIT.  RESTRICTING 
OR BLOCKING A DRAIN LINE WILL DEFEAT THE PURPOSE OF 
THE RELIEF VALVE AND MAY CREATE AN UNSAFE CONDITION.  
INSTALL A DRAIN LINE WITH A DOWNWARD SLOPE SUCH THAT 
IT NATURALLY DRAINS ITSELF.
If any safety relief valve is replaced, the replacement valve must comply 
with the current editions of the ASME Boiler and Pressure Vessel