Important
  1.  The following service procedures are provided as a general 
guide.  
  2.  Meter readings between gas control and ignition module must 
be taken within the trial for ignition period.  Once the igni-
tion module locks out, the system must be reset by setting the 
thermostat down for at least one minute before continuing.
  3.  If any component does not function properly,  make sure it is 
correctly installed and wired before replacing it.
  4.  The ignition module cannot be repaired.  If it malfunctions, it 
must be replaced.
  5.  Only trained, experienced service technicians should service 
intermittent pilot systems. 
Perform the CHECKOUT steps on page 51 as the first step in 
troubleshooting.  Then check TROUBLESHOOTING GUIDE  
to pinpoint the cause of the problem.  If troubleshooting indicates 
an ignition problem, see Ignition System Checks below to isolate 
and correct the problem.
Following troubleshooting, perform the CHECKOUT procedure 
(page 51) again to be sure system is operating normally.
Ignition System Checks
Step 1:  Check ignition cable.
Make sure:
  A.  Ignition cable does not touch any metal surfaces.
  B.  Ignition cable is no more than 36 inches long.
  C.  Connections to the ignition module and to the  igniter-sensor 
are clean and tight.
  D.  Ignition cable provides good electrical continuity.
Step 2:   Check ignition system grounding.
 
Nuisance shutdowns are often caused by a poor or erratic 
ground.
  A.  A common ground, usually supplied by the pilot burner bracket, 
is required for the module and the pilot burner/igniter sen-
sor.
•  Check for good metal-to-metal contact between the pilot 
burner bracket and the main burner.
•  Check the ground lead from GND (BURNER) terminal on 
the module to the pilot burner.  Make sure connections are 
clean and tight.  If the wire is damaged or deteriorated, replace 
it with No.  14-18  gauge, moisture-resistant, thermoplastic 
insulated wire with 105 C (221 F) minimum rating.
•  If flame rod or bracket are bent out of position, restore to 
correct position.
•  Replace  pilot  burner/igniter  sensor  if  insulator  is 
cracked.
Step 3:  Check spark ignition circuit.  You will need a short jumper 
wire made from ignition cable or other heavily insulated 
wire.
  A.  Close the manual gas valve.
  B.  Disconnect the ignition cable at the SPARK terminal on the 
module.
WARNING
When performing the following steps, do not touch stripped 
end of jumper or SPARK terminal.  The ignition circuit 
generates 13,000 volts at 25 pf load and electrical shock 
can result.
  C.  Energize the module and immediately touch one end of the 
jumper firmly to the GND terminal on the module.  Move the 
free end of the jumper slowly toward the SPARK terminal 
until a spark is established.
  D.  Pull the jumper slowly away from the terminal and note the 
length of the gap when sparking stops.  Check table below.
ARC LENGTH
ACTION
No arc or arc less than 1/8 
inch.
Arc 1/8 inch or longer.
Check external fuse, if 
provided.
Verify power at module input 
terminal.
Replace module if fuse and 
power okay.
Voltage output is okay.
Step 4:  Check pilot flame current.
  A.  Turn off furnace at thermostat.
  B.  Disconnect main valve wire from the TH or MV terminal on 
the gas control.
  C.  Disconnect ground wire from GND (BURNER) terminal at 
module.
  D.  Connect a meter (dc microamp scale) in series with the ground 
lead.  
•  Disconnect  ground  lead  from  GND  terminal  on  ignition 
module.
•  Connect  the  black  (negative)  meter  lead  to  the  ignition 
module GND (BURNER) terminal.
•  Connect the red (positive) meter lead to the free end of the 
ground lead.
  E.  Set thermostat to call for heat.  The spark will light the pilot but 
the main burner will not light because the main valve actuator 
is disconnected.
  F.  Read the meter.  The flame sensor current must be steady and 
at least 1.0 uA.
  G.  If the reading is less than the minimum or unsteady,
•  Make sure pilot flame envelopes 3/8 to 1/2 inch of the flame 
rod.  
•  If necessary, adjust pilot flame by turning the pilot adjustment 
screw on the gas control clockwise to decrease or counter-
clockwise to increase pilot flame.  Following adjustment, 
always  replace  pilot  adjustment  cover  screw  and  tighten 
firmly to assure proper gas control operation.
•  Check for cracked ceramic insulator, which can cause short 
to ground, and replace igniter-sensor if necessary.
•  Make sure electrical connections are clean and tight.  Replace 
damaged wire with moisture-resistant No. 18 wire rated for 
continuous duty up to 105 C (221 F).
  H.  Remove  meter  and  reconnect  all  wires.    Return  system  to 
normal operation before leaving job.
INTERMITTENT PILOT TROUBLESHOOTING (continued)