PAN-14 Sensor Installation Guide 
 
Installing the Sensor 
This procedure must be carried out by a certified electrician. 
1. 
Connect the PAN 14 sensor to the CT : 
2. 
Connect the two CT's outputs to the PAN-14 sensor using a 1.0-4.0mm
2
 (12-
17 AWG) wires as follows: 
a.  Connect the PAN-14 sensor's terminal marked as "1" to the CT's 
terminal marked as "S1" or "X1"  
b.  Connect the PAN-14 sensor's terminal marked as "2" to the CT's 
terminal marked as "S2" or "X2"  
 
3. 
Mount the CT on the hot wire: 
a.  If the CT is split-core: 
Close the CT on the hot wire by disconnecting its two parts, and closing 
them around the hot wire. 
b.  If the CT is solid-core: 
Disconnect one of the ends of the hot wire from the panel, insert it 
through the CT, and then reconnect it to the panel. 
c.  In both cases, make sure the CT is placed on the wire so that the 
direction of current flow on the wire is from the side marked "P1" or 
"H1" on the CT, to the side marked "P2" or "H2" on the CT.