Therm-Omega-Tech Inc. 94030 ユーザーズマニュアル
6.7.Alarm Screen
Selects if alarms are on or off (AKA good neighbor feature). The default setting is on.
A L A R M S
O N
O N
6.8.Ramp On/Off Screen
Selects if ramp mode is set to on or off. The default setting is on.
R A M P
O N
6.9.Battery power screen
Shows battery capacity in %.
B A T T P W R
9
9
5 %
7.SUPER USER MENU
Press the scroll key and the up key to enter the Super User Menu.
Press the scroll key and the down key to exit the Super User Menu.
The screens are shown in the order they appear as the scroll key is pressed. When the
Reset All screen is reached and the scroll key is pressed again the menu system will jump
to the selected main screen.
If the unit is left showing any screen for more than 10 seconds it will revert to the
Selected Main Screen.
Press the scroll key and the down key to exit the Super User Menu.
The screens are shown in the order they appear as the scroll key is pressed. When the
Reset All screen is reached and the scroll key is pressed again the menu system will jump
to the selected main screen.
If the unit is left showing any screen for more than 10 seconds it will revert to the
Selected Main Screen.
7.1.Fan % Screen
Shows the current fan duty cycle in %.
F A N
P C T
5 1
%
7.2.Proportional Band Screen
Using the up and down keys the advanced user can adjust the Proportional band from 1-
99 deg F. The default value is 25 deg F. For clarification of this feature see the
definition of terms section at the end of this manual.
99 deg F. The default value is 25 deg F. For clarification of this feature see the
definition of terms section at the end of this manual.
P R O P B A N D
2 5
2 5
D E G
7.3.Offset Screen
Using the up and down keys the advanced user can adjust the Offset from 0-50 deg F.
The default value is 10 deg F. This offset represents a value that is added to the setpoint
The default value is 10 deg F. This offset represents a value that is added to the setpoint