14-11 
 
14.2.5  MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA  
Disharge Procedure 
1.  Turn off the power supply to the outdoor unit. 
2.  After power is turned off, wait for 10 minutes or more. Then remove the electrical parts cover and apply soldering iron of 30 to 
75W for 15 seconds or more to (+) and (-) terminals on system power module, in order to discharge voltage in smoothing 
capacitor 
 
 
 
 
As shown beside, apply soldering iron to metal 
parts (receptacle) inside the sleeve corresponding 
to P1 and N1 terminals of system power module. 
Do this with smoothing capacitors kept connected. 
By removing red/gray lead wire from diode stack, 
power supply can be shut off (corresponding to 
(+) and (-). 
 
 
Do no use a soldering iron with 
transformer: If one is used, thermal fuse 
inside transformer will be blown. 
 
 
14.2.6  MONO SPLIT RAF-25/35RPA / RAC-25/35FPA 
Disharge Procedure 
1.  Turn off the power of the indoor unit or pull out the power supply plug. 
2.   After power is turned off, wait for 10 minutes or more. Then remove the electrical parts cover and apply soldering iron of 30 to 
75W for 15 seconds or more to TAB3 (GRAY) and TAB4 (RED) terminals on the main P.W.B, in order to discharge voltage in 
smoothing capacitor 
 
 
 
Do no use a soldering iron with 
transformer: If one is used, thermal fuse 
inside transformer will be blown. 
 
 
 
 
Smoothing  
Capacitors 
Soldering 
iron 
Lead Wire