Settings and read-off 
parameters  
Code pa-
rameters 
Minimum 
values 
Max. 
values 
Default 
setting 
Operation 
Address 
2 – relay will close after expiration of 
 time or after reduction of con-
sumed wattage to level of 
 whi-
chever is earlier 
Delay of characterizing 
relay closure relatively 
to load relay closure 

300 
 
164 
Allowable load wattless 
power, kVar. 

450 
 
165 
Current protection.  Maximum current protection 
Maximum current 
protection type 



0-protection with independent time de-
lay 
Dependent time delay protection 
types: 
1-SIT; 2-VIT (LTI); 3-EIT; 4-UIT; 5-RI 
166 
Max
 
current
 
protection
 
tripping
 
setting
 
value,
 
ratio 



0,8 
9,0 
2,0 
ratio to the load rated current is as-
signed (functions at i 
P = 0). 
167 
Current protection trip-
ping delay, sec 



0,3 
600 
10,0 
 
168 
Protection   function 
permission 
 



0- protection function prohibited 
1- protection function permitted, after-
tripping automatic reset prohibited 
2- protection function permitted, after-
tripping automatic reset permitted 
169 
Protection against line-to-earth fault (based on zero sequence current iF0) 
Current fault tripping set-
ting, A 

0,3 
5,0 
0,5 
 
170 
Protection
 
tripping
 
delay,s 

0,3 
2,0 
1,0 
 
171 
Protection function 
permission 

0- protection function prohibited 
1- protection function permitted, after-
tripping automatic reset prohibited 
2- protection function permitted, after-
tripping automatic reset permitted 
172 
Voltage protection 
 
 
Minimum line voltage, V 



270 
415 
320 
 
173 
Min voltage de-energize 
tripping delay time, sec 



5  
30  
10  
 
174 
Minimum voltage pro-
tection   function per-
mission 
 



0- protection function prohibited 
1- protection function permitted, after-
tripping automatic reset prohibited 
2- protection function permitted, after-
tripping automatic reset permitted 
175 
Maximum line voltage, V 



330 
475 
415 
 
176 
Max line voltage de-ener-
gize tripping delay time, s 



1  
10 
 
177 
Maximum voltage pro-
tection   function per-
mission 
 



0- protection function prohibited 
1- protection function permitted, after-
tripping automatic reset prohibited 
2- protection function permitted, after-
tripping automatic reset permitted 
178 
Line
 
voltage
 
imbalance,
 


15  
120  
35  
 
179 
Line voltage imbalance 
de-energize tripping delay 
time, sec 


1  
30  
 
180 
Voltage imbalance pro-
tection   function per-
mission 
 


0- protection function prohibited 
1- protection function permitted, after-
tripping automatic reset prohibited 
2- protection function permitted, after-
tripping automatic reset permitted 
181 
Phase sequence pro-

0- protection function prohibited 
182