ОМ-310
 
Settings and read-off 
parameters  
Code pa-
rameters 
Minimum 
values 
Max. 
values 
Default 
setting 
Operation 
Address 
energize, AR prohibited after commu-
nication has been restored 
Response timeout detec-
tion, sec 

120 
0 - prohibited 
198 
 OM-310 communication 
via serial channel permit-
ted 

0-  communication prohibited 
1-  communication  via RS-232 
2-  communication  via MODBUS 
199 
Device version 

 
 
10 
The parameter value depends on the 
firmware version 
200 
Remotely controlled 
load energizing and de-
energizing via RS-
232/RS485 

0 – remote control prohibited 
1- remote control permitted, load relay 
closure permitted after 
ОМ-310 device 
energizing  
2- remote control permitted, load relay 
closure prohibited after 
ОМ-310 power-
on until remote power-on command 
has been issued 
201 
OM-310 Remote Opera-
tion control via remote 
switch 

0 – remote control via the switch 
prohibited 
1-4 see par 2.4.6 
202 
The starter functionality 
monitoring (presence of 
currents when load relay 
is open) 

0- off 
1- on 
203 
 
* Note. The parameter is utilized if the characterizing relay functions in the additional load relay mode (
2) 
 
1.2.4 Operating controls and the dimensions 
of the ОМ-310 are shown in fig.1.1. 
 
 
1 – red LED  - SETUP  glows when the relay is in parameter setup mode 
2 – green LED  - LOAD glows when the load relay is closed 
3 – green LED  - RELAY glows when the characterizing relay is closed 
4 – green LED - MMSP (mode with minimal number of setting parameters) glows when the relay is in MMSP mode 
5 - three-digit parameter mnemonic indication display: 
-  dot glows in the lower case of the display  when 
ОМ-310  device is in service engineer access mode;  
- dot glows in the middle case of the display line when a setup parameter value is secured  by service engineer password; 
- dot glows in the upper case of the display line when a setup parameter is not included in the MMSP list 
6 - three-digit parameter value indication display  
7 – blue LED -  EXCHANGE glows during data exchange with PC 
8 – red LED – FAULT: 
- while load relay is open: the LED glows, when 
ОМ-310 is in fault mode (flickers, when AR after fault is possible); 
- while load relay is closed, the LED flickers when the load consumed input power is over the main threshold, but the load 
relay open  time has not yet been reached 
 
9 - plug connection for connecting 
ОМ-310  to PC via RS-232 
10 – green LED
 
- glows when the 
ОМ-310 characterizing relay works in the mode of controlling additional load (par. 2.4.3) 
11 – green LED - TR glows when the 
ОМ-310 characterizing relay functions in the time relay mode and blinking when 
OM-310 is working in signalization mode  of main tripping exceeding of active power.