Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 データシート

製品コード
OM-310
ページ / 28
- 8 - 
ОМ-310
                                                                                                                                                       
NOVATEK-ELECTRO
 
Settings and read-off 
parameters  
Code pa-
rameters 
Minimum 
values 
Max. 
values 
Default 
setting 
Operation 
Address 
tection   function per-
mission 
 
1- protection function permitted, after-
tripping automatic reset prohibited 
2- protection function permitted, after-
tripping automatic reset permitted 
Load Engagement and Automatic Reset Control 
 
 
Automatic reset (AR) 
time, sec 

900 
 
183 
AR prohibited for all 
faults (except voltage 
faults) 

0 - AR prohibited 
1- AR permitted 
 parameter value is effective for all 
types of faults except voltage faults.  
 
parameters
 
shall
 
be
 
used
 
to
 
prohibit
 
AR in case of voltage
  
faults 
184 
Load relay operation 
permitted after OM de-
vice power-on 

0 – manual load start  from OM-310 
front panel 
1- load start after AR delay time 
load start after 2 sec delay 
185 
Load start/cutoff control 
with use of OM-310 
front panel 

0 - prohibited 
1- load energizing permitted 
2- emergency load de-energizing per-
mitted 
3- load energizing and de-energizing 
permitted  
See par. 2.4.9  
186 
Miscellaneous 
 
 
Time within which av-
erage current value is 
measured, sec 

10 
600 
60 
 Time within which average current 
value is measured (parameters iS1, 
iS2, iS3 from Table 1.5) 
187 
Min number of setting 
parameters mode ena-
ble 

0-mode disabled 
1- mode enabled 
The mode change is enabled in the 
service-engineer mode only. 
188 
Indication on OM-310 
display panel before 
load energize 

1        
0- line voltage Uab 
1-active power PoA 
2-AR time countdown 
189 
Parameter indication 
mode 

1  
0-parameter value indicated continuously 
1-parameter
 
value
 
indicated
 
within
 
15s 
190 
Complete equipment 
operation time, days 


 
999 
 

 
when MODBUS/RS-232 interface data 
transfer is utilized, the operation time 
is transferred in hours  
191 
User access code 

0 – keyboard unlocked 
1-9 – user password 
192 
Service engineer 
access code 

000 
999 
123 
000-access to service engineer level  - 
permitted 
000-999 – service engineer password 
193 
System reset to factory 
settings 

After  value 1 has been recorded  and 
parameter setup mode exited, the fac-
tory set parameters will be restored 
194 
(RS-485/ RS-232) serial interface parameters 
 
 
OM-310 device commu-
nication address 

247 
 
195 
Transfer rate 

0:  9600 baud; 1: 19200 baud; 
Transfer rate change will take effect af-
ter power-off/ and restarting power-on. 
196 
OM-310 response to 
loss of connection 

0-continue without warning  
1- warning message, continue opera-
tion 
2-warning message and load relay de-
energize, AR permitted after commu-
nication has been restored 
3-warning message and load relay de-
197