Reference material 
 
5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
219
 
Parameter 
T: The output is switched off on expiration of the delay time T (output signal 
transition 1 to 0). 
Retentivity on = the status is retentive in memory. 
Output Q 
Q switches on for the duration of the time T after a trigger at input Trg. 
Parameter T 
The actual value of another already-programmed function provides the time set in parameter 
T: 
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta 
●  Wiping relay(pulse output): Ta 
●  Edge triggered wiping relay: Ta 
●  Asynchronous pulse generator: Ta 
●  Stairway light switch: Ta 
●  Multiple function switch: Ta 
●  Stopwatch: AQ 
●  Analog filter: AQ 
●  Average value: AQ 
●  Max/Min: AQ 
●  Threshold trigger: Fre 
You select the required function by the block number. 
For information on the validity and accuracy of the time base, refer to the 
LOGO! Manual