Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
220
 
Operating Instructions, 06/2014 
Timing diagram 
 
Description of the function 
A 0 to 1 transition at input Trg sets output Q to 1 instantaneously. 
At the 1 to 0 transition at input Trg, LOGO! retriggers the current time T, and the output 
remains set. LOGO! resets the output Q to 0 when T
a
 reaches the value specified in T (T
a
=T) 
(off delay). 
A one-shot at input Trg retriggers the time Ta. 
You can reset the time Ta and the output via the input R (Reset) before the time Ta has 
5.3.1.3 
On-/Off-delay 
 
Short description 
The on-/off- delay function block can set an output after a configured on-delay time and then 
reset it again upon expiration of a second configured time.  
 
Connection 
Description 
Input Trg 
You trigger the on-delay with a positive edge (0 to 1 transition) at input Trg 
(Trigger). 
You trigger the off-delay with a negative edge (1 to 0 transition). 
Parameter 
T
H
 is the on-delay time for the output (output signal transition 0 to 1). 
T
L
 is the off-delay time for the output (output signal transition 1 to 0). 
Retentivity on = the status is retentive in memory 
Output Q 
Q switches on upon expiration of a configured time T
H
 if Trg is still set. It 
switches off again upon expiration of the time T
L
 and if Trg has not been set 
again.