5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
222
 
Operating Instructions, 06/2014 
Timing diagram 
 
Description of the function 
A 0 to 1 transition at input Trg triggers the time T
H
If the status at input Trg is 1 for at least the duration of the configured time T
H
, LOGO! sets 
the output to logical 1 upon expiration of this time (output is on-delayed to the input signal). 
The time T
H
 resets if the status at input Trg resets to 0 before this time has expired. 
The 1 to 0 transition at the output triggers the time T
L
 is triggered. 
If the status at input Trg remains 0 at least for the duration of a configured time T
L
, the output 
resets to 0 upon expiration of this time (output is off delayed to the input signal). 
The time T
L
 resets if the status at input Trg returns to 1 before this time has expired. 
5.3.1.4 
Retentive on-delay 
 
Short description 
A one-shot at the input triggers a configurable time. LOGO! sets the output upon expiration 
of this time.  
 
Connection 
Description 
Input Trg 
Trigger the on-delay time via the Trg (Trigger) input. 
Input R 
Reset the on-delay time and reset the output to 0 via input R (Reset). 
Reset takes priority over Trg. 
Parameter 
T is the on-delay time for the output (output signal transition 0 to 1). 
Output Q 
Q switches on upon expiration of the time T.