Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
224
 
Operating Instructions, 06/2014 
Description of the function 
A 0 to 1 signal transition at input Trg triggers the current time Ta. LOGO! sets the output Q to 
1 when Ta reaches the time T. A further pulse at input Trg does not affect Ta. 
The output and the time Ta reset to 0 only with a 1 signal at input R. 
If you do not set the retentivity, output Q and the expired time reset after a power failure. 
Special functions (Page 212)  
5.3.1.5 
Wiping relay (pulse output) 
 
Short description 
An input signal generates an output signal of a configurable length.  
Connection 
 
Connection 
Description 
Input Trg 
You trigger the time for the wiping relay with a signal at input Trg (Trigger). 
Parameter 
T represents the time after which the output resets (output signal transition 1 to 
0). 
Retentivity on = the status is retentive in memory. 
Output Q 
A pulse at Trg sets Q. The output stays set until the time T has expired and if Trg 
= 1 for the duration of this time. A 1 to 0 transition at Trg prior to the expiration of 
T also resets the output to 0. 
Parameter T 
The actual value of another already-programmed function can provide the off time T:  
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: