5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
228
 
Operating Instructions, 06/2014 
Timing diagram 
 
Description of function 
You define the length of the on and off times at the parameter T. The En input enables the 
pulse generator. The pulse generator sets the output to 1 for the duration of the time T, then 
to 0 for the duration of the time T and so forth, until input En = 0. 
Always specify a time T of 0.1 s. A time T is not defined for T = 0.05 s and T = 0.00 s. 
Special functions (Page 212)  
5.3.1.8 
Asynchronous pulse generator 
 
Description of function 
The pulse shape at the output can be modified by a configurable pulse/pause ratio.  
 
Connection 
Description 
Input En 
You enable/disable the asynchronous pulse generator with the signal at input En. 
Input Inv 
The Inv input can be used to invert the output signal of the active asynchronous 
pulse generator. 
Parameter 
T
H
, T
L
: You can customize the pulse width (T
H
) and the interpulse width (T
L
). 
Output Q 
Q is toggled on and off cyclically with the pulse/pause times T
H
 and T
L
Parameters T
H
 and T
L
 
The pulse width T
H
 and the interpulse width T
L
 can be provided by the actual value of 
another already-programmed function: 
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt