Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
230
 
Operating Instructions, 06/2014 
5.3.1.9 
Random generator 
 
Short description 
The output of a random generator is toggled within a configurable time.  
 
Connection 
Description 
Input En 
The positive edge (0 to 1 transition) at the enable input En (Enable) triggers the 
on-delay for the random generator. 
The negative edge (1 to 0 transition) triggers the off-delay for the random 
generator. 
Parameter 
T
H
: The on-delay is determined at random and lies between 0 s and T
H
T
L
: The off-delay is determined at random and lies between 0 s and T
L
Output Q 
Q is set on expiration of the on-delay if En is still set. It is reset when the off-
delay time has expired and if En has not been set again. 
Parameters T
H
 and T
L
 
The on-delay time T
H
 and the off-delay time T
L
 can be provided by the actual value of 
another already-programmed function: 
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta 
●  Wiping relay(pulse output): Ta 
●  Edge triggered wiping relay: Ta 
●  Asynchronous pulse generator: Ta 
●  Stairway light switch: Ta