Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
226
 
Operating Instructions, 06/2014 
Short description 
An input pulse generates a preset number of output pulses with a defined pulse/pause ratio 
(retriggerable), after a configured delay time has expired.  
 
Connection 
Description 
Input Trg 
You trigger the times for the Edge-triggered wiping relay with a signal at input 
Trg (Trigger). 
Input R 
The output and the current time Ta resets to 0 with a signal at input R. 
Parameter 
T
H
, T
L
: The pulse width T
H
 and the interpulse width T
L
 are adjustable. 
N determines the number of pulse/pause cycles T
L
/T
H
Value range: 1 to 9. 
Retentivity on = the status is retentive in memory. 
Output Q 
Output Q sets when the time T
L
 has expired and resets when T
H
 has expired. 
 
 
 
0BA2, 0BA3: 
Only the parameter T
H
 exists. T
H
 represents the off-delay time for the output. 
Input R is not available. 
Parameters T
H
 and T
L
 
The actual value of another already-programmed function can provide the pulse width T
H
 
and the interpulse width T
L
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta 
●  Wiping relay(pulse output): Ta 
●  Edge triggered wiping relay: Ta 
●  Asynchronous pulse generator: Ta 
●  Stairway light switch: Ta