5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
232
 
Operating Instructions, 06/2014 
5.3.1.10 
Stairway lighting switch 
 
Short description 
The edge of an input pulse triggers a configurable time. The output is reset when this time 
has expired. An off warning can be output prior to the expiration of this time.  
 
Connection 
Description 
Input Trg 
You trigger the time (off-delay) for the stairway switch with a signal at input Trg 
(Trigger). 
Parameter 
T : The output is reset (1 to 0 transition) when the off-delay time T has expired. 
T
!
 : determines the triggering time for the prewarning. 
T
!L
 : determines the length of the prewarning time. 
Retentivity on = the status is retentive in memory. 
Output Q 
Q is reset after the time T has expired. A warning signal can be output before 
this time has expired. 
Parameters T, T
and T
!L
 
The off-delay time T, the prewarning time T
!
 and the prewarning period T
!L
 can be provided 
by the actual value of another already-programmed function:  
●  Analog comparator: Ax - Ay 
●  Analog threshold trigger: Ax 
●  Analog amplifier: Ax 
●  Analog multiplexer: AQ 
●  Analog ramp: AQ 
●  Mathematic instruction: AQ 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta 
●  Wiping relay(pulse output): Ta 
●  Edge triggered wiping relay: Ta 
●  Asynchronous pulse generator: Ta 
●  Stairway light switch: Ta