Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
 
LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
155
 
●  Retentive on-delay  (Page 144) (current time Ta) 
●  Wiping relay(pulse output)  (Page 146) (current time Ta) 
●  Edge triggered wiping relay (Page 148) (current time Ta) 
●  Asynchronous pulse generator (Page 150) (current time Ta) 
●  Stairway lightswitch (current time Ta) 
●  Multiple function switch  (Page 156) (current time Ta) 
●  Stopwatch (Page 171) (actual value AQ) 
●  Threshold trigger (Page 180) (actual value Fre) 
Select the required function by the block number. The timebase is configurable. For 
information on valid ranges and parameter defaults, refer to the On-delay (Page 136) topic. 
Timing diagram 
 
Functional description 
A 0 to 1 signal transition at input Trg sets output Q. The next 1 to 0 transition at Trg 
retriggers the current time T
a
, and output Q remains set. 
LOGO! resets output Q when T
= T. You can output a warning signal before the off-delay 
time (T - T
!
) expires to reset Q for the time of the pre-warning period T
!L
A further one-shot at input Trg during T
retriggers the time T
If the block is retentive, LOGO! resets output Q and the expired time to the values before a 
power failure; if the block is not retentive, LOGO! resets output Q and the expired time to 
defaults after a power failure.  
Setting the Par parameter 
Note the defaults specified in topic Time response (Page 128). 
 
 
Note 
All times must have the same timebase. 
 
View in programming mode (example):