EXCEL 500/600 INSTALLATION INSTRUCTIONS 
XP502 with External UPS XAPU 24-2F (Distributed 
I/O and Internal Modules) 
As shown in the figure below, two XAPU 24-2F UPSs are 
required when the controller has both internal and Distributed 
I/O modules connected. 
Fig. 56. Connection of XAPU 24-2F UPS (internal and
Distributed I/O modules) 
XAPU 24-2F number 1 is connected to the XP502 for the 
controller, only. No other devices may be powered by XAPU 
number 1. 
XAPU 24-2F number 2 is connected to the XSL511 
L
ON
W
ORKS
 connector modules for powering the Distributed 
I/O modules. The connection through relay K1 of the XP502 
insures that the power supply to the Distributed I/O modules 
will be switched OFF when the XP502 is switched OFF. 
XF521A Analog Input Module 
Technical Specifications 
Number: 
eight inputs (AI1 – AI8) 
Input: 
0...10 Vdc (low-input impedance, 25kOhm to 10 V /  
200kOhm to GND);  
0...20 mA (via external 500-ohm resistor);  
4...20 mA (via external 500-ohm resistor);  
NTC 20K ohm (-50...+150 °C);  
PT1000 (-50...+150 °C)  
Protection: 
up to 40 Vdc / 24 Vac 
Resolution: 
12-bit resolution 
Accuracy: 
±75 mV or 0.75% (0...10 V) 
Table 7. Accuracy of analog input sensors 
Measurement error (without
Range 
sensor tolerance) 
PT1000 
NTC 20K 
-58...-4 °F (-50...-20 °C) 
≤ 1.2 K 
≤ 5.0 K 
-4...+32 °F (-20...0 °C) 
≤ 0.7 K 
≤ 1.0 K 
+32...86 °F (0...30 °C) 
≤ 0.5 K 
≤ 0.3 K 
86...158 °F (30...70 °C) 
≤ 0.7 K 
≤ 0.5 K 
158...212 °F (70...100 °C) 
≤ 1.2 K 
≤ 1.0 K 
212...266 °F (100...130 °C) 
≤ 1.2 K 
≤ 3.0 K 
266...302 °F (130...150 °C) 
≤ 1.2 K 
≤ 5.5 K 
With current sensors, a terminating resistor of R1 = 499 ohms  
± 0.25 % must be connected.  
Terminal 18 is an auxiliary output voltage (+10 Vdc, I
max
 =  
5 mA) available for various sensor circuits.  
Fig. 57. XF521A Analog Input module connections 