EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Fig. 60. XF526 Analog Input module connections 
XF523A Digital Input Module 
The digital input module can process DC or AC voltage 
signals. The module has 12 digital inputs. When the input 
voltage reaches 5 V, the digital signal is set to a status of "1". 
With a hysteresis of 2.5 V, the digital input signal must fall 
below 2.5 V before a digital status of "0" is reported. 
Fig. 61. Digital input hysteresis 
The LED functionality of each digital input channel can be 
altered via 12 internal DIP switches. In the ON position 
(default), the LED will illuminate when energized (normally 
open contacts). In the OFF position, the LED will illuminate 
when de-energized (normally closed contacts). 
Max. signal voltage from non-Honeywell voltage sources: 
DC Voltage: V
max
 = 40 V 
AC Voltage: V
max
 = 28 V / 
≥ 50 Hz 
Input resistance: 
R
= 15k ohms 
Fig. 62. XF523A connection examples 
If the inputs are used as totalizers, Table 9 applies. 
Table 9. Totalizer inputs specifications 
Input 
Frequency 
Pulse duration 
Pulse internal 
Chatter time 
1, 2 
max. 15 Hz 
min. 20 ms 
min. 33 ms 
max. 5 ms 
3 to 12 
max. 0.4 Hz 
min. 1.25s 
min. 1.25 s 
max. 50 ms 
The inputs shown in row one (Input 1 to 2) may be used as fast totalizers. In this case, the input signal characteristics of row one 
are valid. If they are not used as fast totalizers, the values of row two (Inputs 3 to 12) apply to them as well. 