Honeywell Excell 500/600 Controll System 500-XCL5010 ユーザーズマニュアル

ページ / 48
EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Fig. 58 shows several connection examples for various 
sensors: WS21 Wind Sensor; SAF 25 Solar Sensor; and VMP 
Feedback Potentiometer. 
Fig. 58. XF521A connection examples 
Fig. 59 shows connections to a TF26. 
Terminals 1, 3:  temperature adjustment 
Terminals 5, 3:  room sensor 
Terminals 6, 3:  LED 
XF526 Analog Input Module 
Technical Specifications 
Number: 
eight inputs (AI1 – AI8) 
Input: 
0...10 Vdc (low-input impedance, 25kOhm to 10 V /  
200kOhm to GND);  
0...20 mA (via external 500-ohm resistor);  
4...20 mA (via external 500-ohm resistor);  
NTC 20K ohm (-50...+150 °C);  
PT1000 (-50...+150 °C)  
PT1000 (0...+400 °C)  
PT100 (-50...+150 °C)  
PT3000 (-50...+150 °C)  
Balco 500 (-50...+150 °C)  
Protection: 
up to 40 Vdc / 24 Vac 
Resolution: 
12-bit resolution 
Accuracy: 
±75 mV or 0.75% (0...10 V) 
Table 8. Accuracy of analog input sensors 
Range 
Measurement error (without
sensor tolerance) 
PT1000 
NTC 20K 
-58...-4 °F (-50...-20 °C) 
≤ 1.2 K 
≤ 5.0 K 
-4...+32 °F (-20...0 °C) 
≤ 0.7 K 
≤ 1.0 K 
+32...86 °F (0...30 °C) 
≤ 0.5 K 
≤ 0.3 K 
86...158 °F (30...70 °C) 
≤ 0.7 K 
≤ 0.5 K 
158...212 °F (70...100 °C) 
≤ 1.2 K 
≤ 1.0 K 
212...266 °F (100...130 °C) 
≤ 1.2 K 
≤ 3.0 K 
266...302 °F (130...150 °C) 
≤ 1.2 K 
≤ 5.5 K 
With current sensors, a terminating resistor of R1 = 499 ohms  
± 0.25 % must be connected.  
Terminal 18 is an auxiliary output voltage (+10 Vdc,  
I
max
 = 5 mA) available for various sensor circuits.  
Fig. 59. XF521A and TF26 example 
EN1R-1047GE51 R0902 