Fig. 69. Transformer example 
Use quick-acting backup fuse 10 A (or automatic H16 or L16) 
to protect transformer primary side. On the primary side of the 
CRT 2, there is a fusible output of type M 0.315 A (T) 250 V 
for the purpose of fine fusing. 
NOTE:   When selecting the appropriate transformer, con­
sider the number of Distributed I/O modules (see 
worst-case power consumption information below) to 
be used as well as the power requirements of all 
active sensors and actuators connected to the 
transformer. 
CRT-Series 
Table 12. Overview of CRT Series AC/DC current 
Transformer  max. AC current 
max. DC current 
CRT 2 
2 A 
0.5 A = 500 mA 
CRT 6 
6 A 
1.3 A = 1300 mA 
CRT 12 
12 A 
2.5 A = 2500 mA 
Fig. 70. AC/DC current graphs 
1450 Series 
All transformers of the 1450 series are designed for 50/60 Hz 
AC and have insulated accessory outputs. The transformers 
include built-in fuses, line transient/surge protection and AC 
convenience outlets and meet NEC class 2 requirements. 
EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Table 13. 1450 Series transformers 
Part # 
1450 7287 
Primary side 
Secondary side 
-001 
120 Vac 
24 Vac, 50 VA 
-002 
120 Vac 
2 x 24 Vac, 40 VA and 100 VA 
from separate transformer 
-003 
120 Vac 
24 Vac, 100 VA and 24 Vdc 
600 mA 
-004 
240/220 Vac  24 Vac, 50 VA 
-005 
240/220 Vac 
2 x 24 Vac, 40 VA and 100 VA 
from separate transformer 
-006 
240/220 Vac 
24 Vac, 100 VA and 24 Vdc 
600 mA 
Standard Transformers 
Standard commercially available transformers must fulfill the 
specifications stated in Table 14. 
Table 14. Requirements for standard transformers 
Output voltage 
Impedance 
AC current 
24.5 Vac to 25.5 Vac  ≤ 1.15 ohms 
max. 2 A 
24.5 Vac to 25.5 Vac  ≤ 0.40 ohms 
max. 6 A 
24.5 Vac to 25.5 Vac  ≤ 0.17 ohms 
max. 12 A 
Screw Terminal Block Installation Procedure
 WARNING 
High Voltage 
Risk of death or electrical shock. 
— Do not connect line power supply directly to the 
terminals. 
— Insulate devices with 120 Vac / 230 Vac by a 
transformer. 
1.   Make sure that the power supply of the cabinet is  
disconnected.  
2.   Make sure that the power supply of the cabinet is  
disconnected and the communication module is  
plugged in the housing.  
IMPORTANT 
When installing a separate external transformer, do 
not connect the cabinet ground to the controller 
system ground. 
3.   If the distance between the controller and an actuator or 
sensor with 24 Vac supply is greater than 550 ft 
(170m): 
a)   Choose a transformer from the transformers 
listed in section "Power Supply" on page 32. 
b)  Connect the chosen transformer directly to the 
actuator or sensor. 
33  