EXCEL 500/600 INSTALLATION INSTRUCTIONS 
4.   Select one of the transformers of the CRT-series or 
1450 series from the tables on the previous page or 
take a commercially available standard transformer 
fulfilling the requirements listed in Table 14. 
5.   Make sure that the communication module is attached 
to the controller housing. 
IMPORTANT 
The transformer feeding the Excel 500 Controller 
must be in the same cabinet. For the selection of the 
transformer, the max. DC current must be 
considered if field devices with DC load are used. 
The secondary side of the transformer must not be 
connected to earth ground. 
Fig. 71. Connecting the power supply 
6.   Connect the 24 Vac (-) on the secondary side of the 
transformer to terminal 1 on the Screw Terminal Block. 
7.   Connect the 24 Vac on the secondary side of the 
transformer to terminal 2 on Screw Terminal Block. 
Fig. 72. Connecting to a screw terminal 
IMPORTANT 
If there already are additional transformers, for 
example supplying actuators or active sensors, 
connect the 24 Vac (-) (secondary side) of the 
transformers together. 
8.   Attach the terminal blocks to the housing as shown in 
Fig. 73. Attaching screw terminal block 
Pull-Up Resistor Handling (O.S. 2.04.00 or higher, 
except for XFL521A) 
High-Impedance Sensors and Active Sensors 
When high-impedance sensors and active sensors are  
connected to the inputs, the recognized value will not differ  
significantly from the measured value if the pull-up resistor is  
de-activated as follows:  
Put the character “@” as the first digit of the chosen input  
characteristic name in the CARE text editor.  
Example:  
Characteristic name: @0-10V; the internal pull-up resistor is  
disabled.  
10 Vdc 
200K ohm 
Vi 
ground 
Fig. 74. Analog input / high-impedance sensors 
NTC and Low-Impedance Sensors 
Characteristic name: NTC; the internal pull-up resistor is 
enabled. 
EN1R-1047GE51 RR0902  