EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Excel 500-XCL5010 
The Excel 500-XCL5010 housing comprises a removable 
screw terminal block for direct power supply wiring. For 
proper installation of the terminal block, follow these 
instructions: 
1.   Read the complete chapter "Installation" carefully. 
2.   Follow the instructions from the chapter Screw Terminal 
Block Installation Procedure on page 33. 
The screw terminal block is attached directly to the controller 
housing. 
Fig. 66. Excel 500-XCL5010 terminal block location 
Serial Port 
COMMUNICATION 
MODULE 
C-BUS 
CONNECTOR 
LON-BUS 
CONNECTOR 
SERIAL PORT 
XCL5010 
EXCEL 500-
FOR EXTERNAL MMI, 
HOUSING 
MODEM, OR ISDN 
TERMINAL ADAPTER 
Co
m
m
_P
rt 
Fig. 67. Serial port 
The serial port has a 9-pin sub-D connector and has a default 
communication speed of 9.6 Kbaud. 
Table 11. Signals of serial port 
Signal type 
Controller output 
Controller input 
Signal ground 
Transmit 
Receive 
Carrier detect 
Clear to send 
Data terminal 
ready 
5 V 
MMI Connection 
For direct communication the external operator interface 
XI582 and the PC-based MMI XI584 can be connected to the 
serial port. 
Power Supply 
The Excel 500-XCL5010 controller is powered by an external 
transformer. 
IMPORTANT 
Only the terminals 1 and 2 of the terminal block may 
be used for power supply. Do not wire any of the 
terminals 3 to 14. 
Fig. 68. Excel 500-XCL5010 power terminals location 
Terminal 2 is protected by a 4 A quick-acting fuse. 
Transformer requirements for one Excel 500-XCL5010
Controller: 
Voltage  21 to 26.5 Vdc or 24 Vac ± 20% 
Current  1.6A max. 
The transformer, already installed in the cabinet, can be used 
to supply several controllers, communication devices, or 
peripherals like actuators, etc. if the transformer provides 
sufficient power. 
EN1R-1047GE51 RR0902  
32