EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Fig. 80. Termination Module 209541B connections for a
singly-terminated FTT network 
3
shield 
shield 
4
LON 
Termination 
plug-in
jumper 
FTT/LPT Bus
FTT/LPT Free
Park Position 
removable screw-type 
3-pole terminal block 
O
N
Fig. 81. XAL-Term 
In the case of either a daisy chain or free-topology L
ON
W
ORKS 
bus layout, the maximum lengths described above must be 
adhered to. 
System Bus (C-Bus) 
Up to 30 controllers can communicate with one another and a 
PC central via the system bus. Instead of an Excel 500/600 
controller, other system bus compatible components can also 
be connected. (Excel IRC Multicontroller; Excel EMC). 
The system bus must be connected through the individual 
controllers (open ring). 
Fig. 82. C-bus topology 
IMPORTANT 
Star connection is not permissible because 
uncontrollable line reflections may occur. 
For setting up the system bus in the right way, three steps 
have to be followed: 
1.   Select submodule for system bus communication  
(XC6010, only)  
2.   Specify cable for system bus. 
3.   Set up submodule (XC6010), CPU module (XC5010C), 
or communication module (XCL5010). 
Submodule Selection (XC6010) 
Two submodules for system bus communication are 
available. The selection depends on the communication 
speed. 
Table 18. C-Bus submodule baud rates 
Submodule 
Possible baud rates 
XD505A 
9600 baud 
XD508 
9600 baud 
19200 baud 
76800 baud 
If the system bus speed throughout the system life-time is 
restricted to 9600 baud, then a submodule XD505A should be 
chosen. Otherwise, the XD508 must be used. 
NOTE:   All communication submodules on one bus must be 
of the same type, i.e. either uniquely XD505A or 
uniquely XD508. Do not use a mix between 
submodules XD505A and XD508 on the same bus. 
IMPORTANT 
For communication with more than 9600 baud it is 
required to enable the termination of the first and the 
last device on the C-bus (see the following sections). 
The controllers with termination must be switched 
ON prior to the controllers in the middle of the C-bus. 
The C-bus might not work if the controllers with 
termination are switched OFF. 
The maximum communication speed of the XC5010C / 
XCL5010 is 76800 baud. The XC5010C/XCL5010 can be 
mounted together with the XC6010 (with XD505A or XD508 
submodule) since the XC5010C/XCL5010 communication 
speed can be changed to match either submodule. 
NOTE:   When changing the baud rate of bus devices, proper 
communication cannot be ensured until all bus 
devices are set to the same baud rate again. 
NOTE:   When adding or removing a controller to/from the C-
Bus, it may take up to two minutes to re-initialize the 
bus. During this time, communication on the C-bus is 
lost. 
System Bus Cable Specification 
The maximum cable length is 4000 ft (1200 m). There are 
regional differences as to whether shielded or unshielded 
cable must/can be used. 
IMPORTANT 
In Europe, only shielded cable is permitted, while in 
the US, shielded or unshielded cable can be used. 