EXCEL 500/600 INSTALLATION INSTRUCTIONS 
COMMUNICATIONS 
L
ON
W
ORKS
 Bus Wiring 
Connection between the Distributed I/O modules and the 
CPU are made from the L
ON
W
ORKS
 connector module 
XSL511. The L
ON
W
ORKS
 bus is a 78-kilobit serial link that 
uses transformer isolation so that the bus wiring does not 
have a polarity; that is, it is not important which of the two 
L
ON
W
ORKS
 bus terminals are connected to each wire of the 
twisted pair. 
The L
ON
W
ORKS
 bus can be wired in daisy chain, star, loop or 
any combination thereof as long as the maximum wire length 
requirements given below are met. The recommended 
configuration is a daisy chain with two bus terminations. This 
layout allows for maximum L
ON
W
ORKS 
bus length, and its 
simple structure presents the least number of possible 
problems, particularly when adding on to an existing bus. 
Table 16. Doubly-terminated bus specifications 
Cable type 
Max. bus length 
Belden 85102 
2700 m (8900 ft) 
Belden 8471 
2700 m (8900 ft) 
Level IV, 22 AWG 
1400 m (4600 ft) 
JY (St) Y 2x2x0.8 
900 m (3000 ft) 
TIA568A Categ. 5 24AWG, twisted pair 
900 m (3000 ft) 
NOTES: The cable types listed above are as recommended 
by Echelon in their FTT-10A User Guide. The cable 
recommended by Honeywell is the level IV, 22 
AWG, solid core, nonshielded cable. Belden part 
numbers are 9H2201504 (plenum) and 9D220150 
IMPORTANT 
Do not use different wire types or gauges on the 
same L
ON
W
ORKS
 network segment. The step 
change in line impedance characteristics would 
cause unpredictable reflections on the bus. 
NOTE:   In the event that the limit on the total wire length is 
exceeded, then FTT physical layer repeaters 
(FTT 10A) can be added to interconnect segments 
and increase the overall length by an amount equal 
to the original specification for that cable type and 
bus type for each repeater used. For example, 
adding repeaters for a doubly-terminated bus using 
JY (St) Y 2x2x0.8 cable increases the maximum 
length 3000 ft (900 m) for each repeater. 
On the Excel 500-XCL5010 controller, the L
ON
W
ORKS
 bus 
connections are located on the communication module as 
shown in Fig. 78: 
LON SERVICE BUTTON 
POWER, GRN 
LON SERVICE, RED 
LEDs 
C-BUS TxD, YEL 
C-BUS RxD, YEL 
RESERVED 
C-BUS 
TERMINATION 
SWITCH 
1 2 3  
4 5 6 
LON 
C-BUS 
(non-plenum).  
BUS 
IMPORTANT 
A1 A2
NO
T
 US
E
SH
IE
L
D
C + C ­
00
00
01
24 
It is recommended that ferrules not be used to 
terminate stranded wires to be inserted in the 
Distributed I/O Terminal blocks spring-clamp 
terminals. 
The FTT specification includes two components that must be 
met for proper system operation. The distance from each 
transceiver to all other transceivers and to the termination 
must not exceed the maximum node-to-node distance. If 
multiple paths exists, the maximum total wire length is the 
total amount of wire used. 
Table 17. Free topology (singly-terminated) specifications 
Cable type 
Max. node-to-
node distance 
Max. total wire 
length 
Belden 85102 
1650 ft (500m) 
1650 ft (500m) 
Belden 8471 
1300 ft (400m) 
1650 ft (500m) 
Level IV, 22AWG 
1300 ft (400m) 
1650 ft (500m) 
JY (St) Y 2x2x0.8 
1050 ft (320m) 
1650 ft (500m) 
TIA568A Category 5 
24AWG, twisted pair 
825 ft (250m) 
1500 ft (450m) 
Fig. 78. Excel 500-XCL5010 communication module 
L
ON
W
ORKS
 Bus Termination 
Depending upon the configuration, either one or two 
termination modules are required for terminating a L
ON
W
ORKS 
bus with FTT devices on it. The following two different 
L
ON
W
ORKS
 termination units are available for this purpose: 
•  209541B 
L
ON
W
ORKS
 Bus Termination Module (see Fig. 
79 and Fig. 80) and 
•  XAL-Term 
L
ON
W
ORKS 
connection and termination 
module (see Fig. 81), which can be mounted on DIN rails 
and in fuse boxes. 
Fig. 79. Termination Module 209541B connections for
doubly-terminated FTT network 
EN1R-1047GE51 RR0902  