EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Inside the cabinet: 
J-Y-(ST)Y 2 x 2 x 0.8 
Outside the cabinet: 
A-Y-(ST) 2 x 2 x 0.8 
In principle, data transmitting cables should be shielded in 
case of RFI.  
The following summarizes cable types and gives selection  
guidance. Note that baud rate and maximum bus length are  
related to each other.  
Table 19. C-Bus cable types 
Cable type 
Description 
Recommended for 
J-Y-(ST)Y 
2 x 2 x 0.8 
shielded, 
twisted pair 
Europe 
Inside cabinet 
A-Y-(ST)Y 
2 x 2 x 0.8 
shielded, 
twisted pair 
Europe 
Outside cabinet 
AK 3702 
unshielded, 
twisted pair 
US 
not approved for Europe 
AK 3740A 
shielded 
US (low-cost) 
not approved for Europe 
Belden 9842  twisted pair 
Europe 
US also possible 
Belden 9841  shielded 
US 
AK 3702 
unshielded, 
twisted pair 
US 
not approved for Europe 
AK 3740A 
shielded 
US (low-cost) 
not approved for Europe 
Each end of the shield on the C-Bus should be connected to 
the shield terminal of the respective device. Do not connect it 
to the cabinet ground or any other ground points. 
C-Bus Extension by Using Repeaters 
The C-Bus length can be extended by using repeaters. Each 
repeater extends the bus length by 4000 ft (1200 m). 
For the US the repeater is available either with or without 
housing. In Europe, only the version with housing is allowed. 
Table 20. Order no. for repeaters 
Description 
US order No. 
European order no. 
without housing 
14507324-001 
-
with housing 
14507324-002 
XD509 
C-Bus Termination (Excel 600) 
The XC6010 CPU module may have either the XD505A or 
the XD508 submodules mounted on them for C-Bus 
communication. Table 18 provides baud rate information for 
selecting the module. 
The XD508 submodule is equipped with a DIP switch which 
activates (ON position) deactivates (OFF position) a 
terminating resistor. Depending on where the controller is 
located on the bus the DIP switch settings must be as follows: 
Table 21. XD508 DIP switch settings for C-Bus
termination 
Controller location 
DIP switch setting 
beginning or end of bus 
ON 
middle of bus 
OFF 
C-Bus Termination (Excel 500) 
The XC5010C CPU module contains a switch for setting 
different C-Bus baud rates. 
Fig. 83. XC5010C C-Bus termination switch location 
The bus termination switch for setting the baud rate has three 
settings: 
Table 22. XC5010 C-Bus termination switch settings 
Switch 
setting 
Baud rate 
Notes: 
S1 
up to 76800 baud 
with bus termination 
same functionality as 
XD508A, up to 76800 baud 
S2 
up to 76800 baud 
without bus 
termination 
same functionality as 
XD508A, up to 76800 baud 
S3 
up to 9600 baud 
same functionality as 
XD505A - Default setting 
C-Bus Termination (Excel 500-XCL5010) 
The communication module for the XCL5010 is equipped with 
a DIP switch for the C-Bus to set the bus termination 
appropriate for the communication speed. 
EN1R-1047GE51 RR0902 