Patterson-Kelley MACH-05 ユーザーズマニュアル

ページ / 59
  MACH®  Series
 
Gas-Fired Boiler 
Operation 
 
 
Page  28 
4.0  OPERATION 
 
4.1
  
G
ENERAL
 
 
4.1.1  Control Panel Front 
 
 
Control Panel 
 
Become familiar with the basic operation of the boiler.  
The front of the control panel shows Operating 
Instructions. 
 
4.1.2  Tests 
Safe lighting and other performance criteria were met 
with the gas manifold and control assembly provided 
on this boiler when the boiler underwent tests 
specified in ANSI Z21.13/CSA 4.9, latest edition.  
(See "Factory Firetest" label.) 
 
4.2
  
N
ORMAL 
L
IGHTING AND 
S
HUT
-D
OWN 
P
ROCEDURES 
 
 
 
If a fault is indicated please refer to 
Troubleshooting, Section 5.5,
 to determine the 
cause of the fault prior to start up. 
 
WARNING!  
Do not use this boiler if any part has been under 
water.  Immediately call a qualified service 
technician to inspect the boiler and to replace any 
part of the control system and any gas control 
which has been under water. 
 
4.2.1  Lighting Procedures 
 
1.  Close main gas valve. 
2.  Turn On-Off switch to "OFF" position. 
3.  Wait 5 minutes. 
4.  Open main gas valve. 
5.  Turn On-Off switch to "ON" position. 
6.  Push reset button on display panel if required. 
7.  Push reset on low gas pressure switch and high gas 
pressure switch. 
The controller will now complete the automatic firing 
sequence.  
 
 
4.2.2  Normal Shut Down Procedures 
1.  Close all manual gas valves. 
2.  Turn off electric power.