Toshiba VF-AS1 ユーザーズマニュアル

ページ / 326
!
K
-3
!
!
E
6
5
8
1
3
0
1
11
 
2. Basic parameter [3/4] 
Sensorless vector/vector with sensor (
Ɣ:Effective, -:Ineffective) 
Title 
Communi
cation 
No. 
Function 
Adjustment range 
Minimum 
setting unit 
(Panel/Communi
cation)
Default 
setting
Write during 
running 
Vector control
PM 
control
V/f 
Reference
Speed 
control
Torque 
control
VJT
0600 
Motor electronic thermal 
protection level 1
10~100% 
1/1 
100 
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 14 
QNO
0017 
Electronic thermal 
protection characteristic 
selection 
Setting Motor type
Overload 
protection
OL stall 
1/1 
Enabled
Ɣ/Ɣ
5. 14 
Ɣ
Ɣ 
5. 14 
Standard 
Motor 
ż (protect) 
× (No stall) 
ż (protect) 
ż (stall) 
× (No Protection) × (No stall) 
× (No Protection)
ż (stall) 
VF Motor
ż (protect) 
× (No stall) 
ż (protect) 
ż (stall) 
× (No Protection) × (No stall) 
× (No Protection)
ż (stall) 
FURW
0701 
Current/voltage unit 
selection
0:%, 1:A (ampere)/V (volt) 
1/1 
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 15 
HOUN
0005 
FM terminal meter 
selection
0~76 *1 
1/1 
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 16 
HO
0006 
FM terminal meter 
adjustment
1/1 
*4 
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 16 
COUN
0670 
AM terminal meter 
selection
0~76 *1 
1/1 
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 16 
CO
0671 
AM terminal meter 
adjustment
1/1 
*4 
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 16 
EH
0300
PWM carrier frequency
1.0~16.0kHz (2.5~8.0kHz) *2
0.1/0.1
*3
Enabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ
5. 17
WXU
0301
Auto-restart control 
selection 
0:Disabled
1:At auto-restart after momentary stop 
2:When turning ST on or off 
3:1+2 
4:At start-up
1/1 
Disabled
Ɣ/Ɣ
Ɣ/Ɣ
Ɣ
Ɣ 
5. 18.1 
WXE
0302
Regenerative power 
ride-through control 
0:Disabled
1:Power ride-through 
2:Deceleration stop during power failure   
3:Synchronized deceleration/acceleration (synchronized 
acceleration/deceleration signal) 
4:Synchronized deceleration/acceleration (synchronized 
acceleration/deceleration signal+power failure) 
1/1 
Disabled
Ɣ/Ɣ 
-/- 
Ɣ
Ɣ 
5. 18. 2
*1: Ÿ For the adjustment range, see the table on page K-40. 
*2: For 200V-55/75kW models and 400V-90kW to 400V-500kW models, the carrier frequency is between 2.5 and 8.0kHz inclusive. 
*3: Default values vary depending on the capacity. Ÿ See the table of K-48. 
*4: Default setting value is adjusted for connection of frequency meters "QS60T". (Between FM and CCA: Approx. 3.6V) (Between AM and CCA: Approx. 3.6V)