SECTION II 
 
MASONRY INSERT INSTALLATION 
 
The Model 81 may be installed using an all masonry  fireplace  built  in accordance with the 
Uniform  Building  Code  and National  Fire Protection Association (NFPA).  The first step  in  
this  type of installation is to determine acceptability of fireplace and chimney for use with a 
woodstove. Both construction and condition of fireplace are important consid-
erations  when  installing a woodstove. The chimney should extend at  least 3'  above roof and 
at least 2' above any point of  roof  within 10'. 
 
CAUTION 
 
REMEMBER  TO HAVE YOUR CHIMNEY INSPECTED FOR  LEAKS AND  BLOCKAGE 
BEFORE YOU INSTALL YOUR STOVE. “DO NOT CONNECT THIS UNIT TO A 
CHIMNEY FLUE SERVING ANOTHER APPLIANCE.” 
 
                 MINIMUM CLEARANCE MASONRY INSERT
 
 
 
A.  Side Wall Combustible 
B.  Front Floor Protector 
C.  Side Floor Protector 
D.  Side Wood Trim 
E.  Top Wood Trim 
F.  Mantel or Brackets 
 
 
12" 
16" 
  8" 
  7" 
10" 
21" 
MODEL 81
 
 
1.  The hearth must be of masonry construction and  must extend a  minimum of 16" in front of 
firebox opening and a minimum of 8"  to either side of firebox opening. 
2.  If there is not minimum hearth protection from front of  firebox opening and front of  
      masonry hearth, a  floor protector must be used in front of hearth to protect  combustible  
      materials.  The floor protector must be 3/8" minimum thickness non-combustible material  
      or equivalent.(See Page 6).
 
F
B
A
E
C
D
 