Honeywell VCR DCP200 ユーザーズマニュアル

ページ / 184
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009
Recorder Option
Page 65
8 The USB Interface
The features covered in this section of the manual are available on models fitted with the 
optional USB Interface or the Data Recorder (which includes the USB Interface).
Using the USB Port
The USB Interface option allows the user to upload or download instrument settings to or 
from a USB memory stick. This allows easy configuration of multiple instruments by copying 
from one to another, or  to transfer it to or from the PC configuration software. If the Data 
Recorder or Profiler options are fitted, recordings and profile information can also be 
transferred via USB memory stick. Refer to the USB Menu section for more details. 
USB Memory Stick Folders & Files
When a USB stick is inserted, the instrument looks for, and if necessary creates the DEVICE
CONFIGPROFILE and RECORDER folders. Files must be located in these folders in order 
to be used. When preparing to upload files from your PC, ensure that you save them to the 
correct folder on the memory stick.
DEVICE – This folder must be located in the 
Root of the USB memory stick
CONFIG – Configuration files (*.bct)
PROFILE – Profile program files (*.pfl)
RECORDER – Recorder log folders/files The 
user is asked for a new recorder sub-folder 
name before transferring recorder data to USB. 
The instrument stores the log files (*.csv) in this 
folder.
CAUTION:
If the file or folder named already exists, data will be overwritten
The first recorder log file written is named 000001-1.csv and placed in the new Recorder 
sub-folder. Stopping/starting a recording does not create a new file, but each time the
parameters being recorded are changed a new file is created (e.g. 000002-1.csv then 
000003-1.csv etc). If any of these files would exceed the maximum spreadsheet size of
65500 data lines, a new file is created with the last digit incremented by 1 (e.g. 000001-2.csv 
then 000001-3.csv).
Note:
To speed up the disk operation, keep the number of files in these folders to a minimum.
CAUTION:
Do not remove the memory stick from the USB port whilst a data transfer operation 
is in progress. Data loss or corruption may result.