Falcon MONITORING F110 ユーザーズマニュアル

ページ / 36
www.rletech.com
24
970.484.6510
3
  F110 Web Interface
3.3.4  Channel 2, Channel 3 and Channel 4
The Channel 2, Channel 3 and Channel 4 tabs are used to configure sensor labels and to set 
temperature thresholds, temperature/humidity thresholds and/or alarm states for the sensors 
connected to sensor channels 2, 3 and 4 on the front of the F110. Sensor labels can be up to 14 
characters in length. 
Depending on whether an external temperature / humidity sensor, external temperature sensor 
or any additional external sensor is plugged into the sensor channel, configuration of each 
specific channel may vary. 
3.3.4.1 External Temperature/Humidity
High and low thresholds can be defined for each temperature/humidity sensor. If the current 
temperature and/or humidity rises above the high threshold or falls below the low threshold, an 
alert will be generated. When the temperature and/or humidity returns to a normal state, the alert 
will clear and a follow-up notification will be sent.
The temperature/humidity sensors can be calibrated, if necessary, by entering correction values 
in the Adjust field for each temperature/humidity sensor. Temperature corrections entered here 
can only be entered in degrees Celsius (i.e. °Celsius = [5/9]*[°Fahrenheit-32]). Humidity 
corrections are entered in percent (%) Relative Humidity. To adjust the temperature and/or 
humidity down, enter a minus (-) sign before the value (i.e. -5). All temperature alert thresholds 
must be entered in degrees Fahrenheit and all humidity alert thresholds must be entered in 
percent (%) Relative Humidity.
Field
Temperature Units
High
Fahrenheit
Low
Fahrenheit
Adjust
Celsius