Falcon MONITORING F110 ユーザーズマニュアル

ページ / 36
www.rletech.com
25
970.484.6510
3
  F110 Web Interface
Figure 3.6 Sensor Settings
3.3.5  Switched Sensor Alarm Configuration
The Channel 1 tab is used to configure sensor labels and alarm states (normally open or closed) 
for the eight (8) switch sensor ports (dry contact inputs) on the back of the F110 unit. Sensor 
labels can be up to 15 characters in length. 
Alert Thresholds for switch sensors connected to the eight (8) sensor ports on the back of the 
F110 are set by specifying either CLOSED or OPEN. Please refer to the documentation 
received with any sensor purchased to determine the 'normal' state (open or closed) for that 
specific sensor type. Next, select the opposite state (i.e. not normal) to configure the F110 for 
its alarm state, which will cause it to send an alert when the alarm condition exists.
3.3.6 Security
The Security tab is used to configure password security for access to the F110 Settings Screen. 
Passwords can ONLY contain the alphanumeric characters “0-9”,”'a-z” and “A-Z”. Spaces, 
symbols, and punctuation are not supported. Be sure to record the password entered here in a 
secure location.