Precision Trading 60 R3.0 ユーザーズマニュアル

ページ / 62
Operator Manual, Supercharger 60 
R3.0 
 
Page 12 of 62 
3. SPECIFICATIONS 
3.1  CHARGE 
3.1.1.  CONTROL: SCR, air cooled. 
3.1.2.  MAXIMUM CURRENT: 50 AMPS. 
3.1.3.  MINIMUM INCREMENT: 0.1 AMP. 
3.1.4.  ACCURACY and STABILITY of settings: ±1% of reading, ±0.1 AMP. 
3.1.4.1.  FLOAT: 
•  The reference voltage is set at the equivalent of 2.33V/cell (Lead-
Acid). 
•  The Cell Selector provides the basic reference as nominal battery 
voltage, e.g.: a 24V battery is entered as 24 on the Cell Selector. 
•  Current reduction from within 0.5V of the float voltage, with an 
accuracy of ±0.5%, ±0.1A 
3.1.4.2.  PEAK:  
•  The reference voltage is set at the equivalent of 2.45V/cell (Lead-
Acid). 
•  The Cell Selector provides the basic reference as nominal battery 
voltage, e.g.: a 24V battery is entered as 24 on the Cell Selector. 
•  Voltage transfer or stop within " 1% of the Peak Voltage. 
•  Note: Due to cable/connector losses the peak voltage registered by 
the Charger-Analyzer will be higher than the actual battery voltage 
(up to 0.2V depending on current).