Precision Trading 60 R3.0 ユーザーズマニュアル

ページ / 62
Operator Manual, Supercharger 60 
R3.0 
 
Page 18 of 62 
4. 
CONTROLS AND DISPLAYS 
4.1  M1 - Ammeter 
4.1.1.  0 to 199.9ADC DIGITAL PANEL METER. 
4.1.2.  Positive sign indicates charge current.  
4.1.3.  Minus sign indicates discharge current. 
4.2  M1 - Voltmeter 
4.2.1.  0 to 1.999VDC, 0 to 19.99VDC and 0 to 199.9VDC DIGITAL PANEL METER. 
4.2.2.  Indicates battery voltage in the internal (20/200V) position and voltage present at 
the RED (+) and BLK (-) jacks in the 2/20/200V external positions. Positive sign 
indicates proper battery connection. Minus sign indicates reversed polarity 
connection. 
4.3  R1 - Main Charge Current Selector 
4.3.1.  Ten turn potentiometer with digital readout to program: current 
4.3.1.1.  MAIN charge current, 0 to 50.0 AMPS. 
4.4  R2 - Topping/Discharge Current Selector 
4.4.1.  Ten turn potentiometer with digital readout to program:  
4.4.1.1.  TOPPING charge current, 0 to 50.0 AMPS 
4.4.1.2.  DISCHARGE current, 0 to 60.0 AMPS 
4.5  SW1 - Main Time selector switch 
4.5.1.  0 to 9 hours (or minutes), to determine the duration of the main charge. 
4.6  SW2 - Total Time selector switch 
4.6.1.  0 to 60 hours (or minutes), to determine the total charge or discharge duration. 
4.7  SW3 – Keypad 
Five station membrane push button control switch to select and control the mode of 
operation, as follows: 
4.7.1.  GREEN: Stop/reset, cycle end. 
4.7.2.  WHITE: Two rate charge mode (main and topping). 
4.7.3.  YELLOW: Single rate charge mode. 
4.7.4.  BLUE: Auto cut-off discharge (analysis). 
4.7.5.  RED: Full discharge (deep cycle).