Precision Trading 60 R3.0 ユーザーズマニュアル

ページ / 62
Operator Manual, Supercharger 60 
R3.0 
 
Page 19 of 62 
4.8  SW4 - CELL SELECTOR: 
4.8.1.   Two digit selector to program the battery terminal voltage as a function of the 
number of cells. 
4.8.2.  Rate: 1.75 volts per cell for charge and 1.0 volts per cell for discharge.  
4.8.3.  Used also in the Float and Peak Voltage modes to enter nominal battery voltage. 
4.9  SW5 - DIGITAL VOLTMETER INPUT SELECTOR: 
4.9.1.  External, 2/20/200V scale. 
4.9.2.  Internal, 20/200V scale. 
4.10  SW6 - VOLTAGE MODE SELECTOR: 
4.10.1.  Four position switch to select Normal, Float and Peak Voltage modes. 
4.11  SW7 - TIMER SPEED SELECTOR:  
4.11.1.  Three position switch to select 
4.11.1.1.  Normal (HH:MM) 
4.11.1.2.  FAST (MM:SS) 
4.11.1.3.  TEST (SS:S/60).