INSTAllATION
INSTAllATION lOCATION RECOMMENDATIONS
Thermostat should be mounted:
•  On an interior wall, in a frequently occupied space.
•  Approximately 5‘ above floor.
•  At least 18” from outside wall.
•  Thermostat can be mounted to a vertical junction box.
Do not mount thermostat:
•  Behind doors, in corners or other dead air spaces.
•  In direct sunlight, near lighting fixtures, or other 
appliances that give off heat .
•  On an outside or unconditioned area wall.
•  In the flow of a supply register, in stairwells, or near 
outside doors .
•  On a wall with concealed pipes or ductwork. 
OUTDOOR TEMpERATURE SENSOR (INClUDED)
Heat pump models can use the outdoor temperature to effectively utilize the heat pump:
•  When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only 
auxiliary heating will be used. 
•  When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and 
only the heat pump will be used to provide heating .
Indoor Air Quality functions can use the outdoor temperature sensor to:
•  Control humidification setpoint based on outdoor temperature to prevent condensation
•  Lock out humidification for temperatures over 60°F or below -30°F.
•  Lock out ventilation based on high and/or low outdoor temperatures.
•  Display outdoor temperature on thermostat.
Outdoor temperature sensor should be mounted:
•  On side of building out of direct sunlight (north side recommended).
•  Above snow line.
•  At least 3’ away from exhaust vents and condensing lines.
•  Using less than 300’ of wire.
•  Do not route wires along 120 VAC lines.
T2
T1
S1
C
I2
L S2
W2
R
RC
W
I1 O/B Y Y2 G
REMOTE TEMpERATURE SENSOR (OpTIONAl)
A remote temperature sensor can be used if the thermostat has to be mounted in a concealed location . A 8051 flush 
mount or 8053 surface mount remote temperature sensor can be attached to the T1 and T2 terminals and mounted 
in a recommended area . The remote sensor must be enabled in the installer setup menu . When the remote sensor is 
installed it overrides the internal sensor .
Do not mount remote sensor:
•  Behind doors, in corners or other dead air spaces.
•  In direct sunlight, near lighting fixtures, or other 
appliances that give off heat .
•  On an outside or unconditioned area wall.
•  In the flow of a supply register, in stairwells, or near 
outside doors .
•  On a wall with concealed pipes or ductwork. 
•  Near 120 VAC lines.
T2
T1
S1
C
I2
L S2
W2
R
RC
W
I1 O/B Y Y2 G
Outdoor temperature can be measured by attaching the included 8052 sensor to the S1 and S2 terminals . The 
outdoor sensor must be enabled in the installer setup menu . 
Remote temperature sensor should be mounted:
•  On an interior wall, in a frequently occupied space.
•  Approximately 5‘ above floor.
•  At least 18” from outside wall.
•  Using less than 300’ of wire.
THERMOSTAT MOUNTINg
1 .  Remove the rear mounting plate from the thermostat . 
2 .  Pull wires through the opening on the back of the 
thermostat .
3 .  Position and level the mounting plate of the thermostat 
on wall and mark the hole locations with a pencil .
4.  Drill 1/4” holes and insert supplied anchors  
(drywall only) .
5.  Place mounting plate over anchors, insert and tighten 
screws .
6 .  Seal wire entry holes to prevent drafts affecting 
temperature readings .
INSTAllATION