MDS-D-SVJ3/SPJ3 Series Instruction Manual
2-7 Connection of regenerative resistor
2 - 33
2-7 Connection of regenerative resistor 
2-7-1 Standard built-in regenerative resistor (Only for MDS-D-SVJ3)
The built-in regenerative resistor is connected by short-circuiting between the P and D terminals of the 
control circuit terminal block (TE2). (Shipment state). Confirm that a short wire has been connected between 
the P and D terminals.
2-7-2 External option regenerative resistor
(1)Servo drive unit
Disconnect the short wire connected between the P and D terminals, and connect the external option 
regenerative resistor unit P-C between the P and C terminals. The drive unit has an internal regenerative 
resistor electronic thermal (software process), and when overheating of the regenerative resistor is detected, 
an over-regeneration (alarm 30) is detected. The thermal protector terminals (G3, G4) are used when 
double-protecting against overheating of the regenerative resistor. When double-protecting, construct a 
sequence in which an emergency stop occurs if a current stops flowing between G3 and G4.
MDS-D-SVJ3 
CNP2
 
P
C
 
D
 
 
Confirm that a short wire has been
connected between the P and D terminals.
Built-in
regenerative resistor
 
P
 
C
 
G4
 
G3
 
×
 
×
 
 
MDS-D-SVJ3
CNP2
P
D C
G3 and G4:
Thermal protector terminals
The current stops flowing
between G3 and G4 when there is
abnormal overheating.
Contact capacity: 150mA
Contact ON resistance: 10mΩ
Twist the wires.
5m or less
Disconnect the
short wire.
External option
regeneration
resistance unit