VOLTAGE REGULATOR (OPTION)
All panels include automatic voltage regulation as 
standard. There are various settings that can be 
made to the voltage regulator via GenLink. The set-
tings are normally factory preset and are shown here 
for completeness.
Voltage KP/KI/KD — Voltage regulation stability 
constants.
PMG — YES indicates a Permanent Magnet Excited 
alternator.
VF Corner 1 / 2. — These are used for v/f control 
to reduce the output voltage when a large load is 
applied that slows down the generator. If the fre-
quency drops below these setpoints, the voltage 
is reduced proportionally as the frequency drops 
according to the Volts per Hertz ratio.
Panel Type — Indicates the panel type that the H-
100 Control Panel has been programmed to be. It 
will normally be H-100.
Volts per Hertz — Number of volts to reduce the 
generator voltage for each hertz below VF Corner 
1 frequency.
AVR Dump Improve — Makes the regulator mod-
ule increase the gain temporarily on a load dump 
to improve the transient voltage response.
Unit Rated Power — This is the generator’s rated 
power in kW.
Voltage Regulator (Option) Chart
 NO. 
PARAMETER 
UNITS
 1 
Voltage 
KP 
-
 2 
Voltage 
KI 
-
 3 
Voltage 
KD 
-
 4 
PMG 
Y/N
 
VF Corner 1 
Hertz
 
VF Corner 2 
Hertz
 7 
Panel 
Type 
-
 
Volts per Hertz 
V/Hertz
 
AVR Dump Improve 
Y/N
 
10 
Unit Rated Power 
kW
GOVERNOR (SPEED REGULATOR) 
OPTION
All panels include automatic frequency (speed) regu-
lation as standard. There are various settings that 
can be adjusted for the governor via GenLink, these 
include the target frequency. The settings are normal-
ly factory preset and are shown here for complete-
ness, they do not apply to all governor types.
Standby KP,KI,KD — Frequency regulation stability 
constants used for normal mode operation.
QuietTest® KP,KI,KD — Frequency regulation sta-
bility constants used for QuietTest® mode opera-
tion.
Actuator Type — Indicates the type of governor 
actuator. The following types are available:
- POWERFLOW — Barber Coleman Powerflow, 
voltage driven without position feedback
-  BOSCH GAS — Bosch Butterfly, current driven 
with position feedback
- LINEAR CURRENT — Linear, Current Driven 
without position feedback
-  DETROIT DIESEL — Detroit diesel PWM Driven
-  BOSCH HORIZONTAL DIESEL — Bosch Diesel 
Arm with Horizontal Connecting Rod and current 
driven with position feedback
-  BOSCH VERTICAL DIESEL — Bosch Diesel Arm 
with Vertical Connecting Rod and current driven 
with position feedback
Actuator Offset — Number corresponding to lowest 
actuator position (Close Throttle).
Actuator Fullscale — Number corresponding to 
highest actuator position (Open Throttle).
Actuator Normal Start Position — The position 
the actuator will be parked at from start up until 
the “Start detection RPM” is reached. If “soft start” 
is enabled, this is also the maximum position of 
the throttle until the Target Frequency - 3 Hz is 
reached. Therefore, if “soft start” is enabled, the 
actuator start position MUST be high enough to 
reach, Target Frequency - 3 Hz.
Actuator QuietTest® Start Position — The position 
the actuator will be parked at from start up until 
the “Start detection RPM” is reached. If “soft start” 
is enabled, this is also the maximum position of the 
throttle until the QuietTest® Target Frequency - 3 
Hz is reached. Therefore, if “soft start” is enabled, 
the actuator start position MUST be high enough 
to reach, QuietTest® Target Frequency - 3 Hz.
Soft Start Time — The time to stay at each soft 
start step before moving on to the next step. ( Only 
applies if soft start is enabled ).
Soft Start Frequency — An entry of 0 Hz disables 
soft start. Any other value enables soft start which 
ramps up the generator frequency at a rate deter-
mined by “Soft Start Time” to minimize smoke. 
This value selects the first frequency to target after 
start up. Once this frequency is attained, the gen-
erator will hold this frequency for the “Soft Start 
Time” and then move to the next step. Each step 
is 3 Hz higher with the final step being “Target 
Frequency” - 3 Hz. Each step is held for the “Soft 
Start Time”. During soft start, the throttle will not 
be allowed to exceed the “Actuator Start Position”.
Diesel — Indicates if this is a diesel powered gen-
erator. This modifies such features as frequency 
control, and others.
  8
General Information
H-100 Control Panel Technical Manual