ENGINE MANAGEMENT
The engine management module is very similar to 
that used in the manufacturer's other products. It 
controls engine cranking, engine starting, engine 
running and engine stopping. These functions are 
performed to a set of “rules” that can be customized 
via parameters from GenLink. In turn, the module 
needs to know certain things about the engine which 
it expects to be programmed in from GenLink.
GENERATOR PARAMETERS
Engine Flywheel Teeth — Number of flywheel teeth 
or pulses per revolution for RPM input. RPM 1 is 
used for the engine controllers.
CT Ratio/Generator — Current Transformer ratio 
for the generator. This value is the result from 
reducing the CT ratio. E.G. If the CT ratio is 
100 amps to 5 amps, the resulting value is 20. 
Normally, the CT ratio will be x amps to 1 amp on 
H-100 Control Panels.
Generator Phase Configuration — Select either 
single-phase or three-phase configuration depend-
ing on how the unit is supplied.
60 Hertz RPM — The engine RPM needed to supply 
60 Hertz power.
Quiet-Test
®
 RPM — The engine RPM used when 
running Quiet-Test
®
.
ENGINE SETTINGS
All of the following times are in seconds:
Preheat Time — The time preheat is applied for 
before cranking if enabled.
Start Detection RPM — The Engine must reach this 
RPM before disengaging the starter.
Crank Time — The maximum time in seconds that 
each crank will last
Alarm Hold-off Time — The time after starting at 
which the hold-off alarms become enabled.
Engine Warmup Time — The engine will run for 
at least this time before issuing the “Accept load” 
signal.
Target Frequency — The target generator frequency 
(Hz).
Target Voltage — The target generator voltage 
(RMS).
‹
‹
Preheat Enable — The following four options are 
selectable (only for Diesel):
- Preheat disabled.
-  Preheat during cranking.
-  Preheat before and during cranking.
- Preheat before and during cranking and until 
load ready.
   The Preheat output pin shares its function with the 
Air/Fuel Solenoid output. You must choose one of 
the two functions as follows:
-  To select Air/Fuel - set the “Diesel” parameter on 
the governor settings page to “No”. Set Preheat to 
“Disabled”
-  To select Preheat - set the “Diesel Y/N” param-
eter on the governor settings page to “Yes”. Set 
Preheat to one of the enable selections.
Engine Cooldown Time — The generator will run 
for at least this time after remote start becomes 
inactive.
Pause Between Cranks Time — The time between 
each successive crank operation.
Number of Start Attempts — The maximum num-
ber of times the engine will attempt to start (crank) 
before faulting out with overcrank.
Load Accept Frequency — The generator must 
reach this frequency before issuing the “Accept 
load” signal.
Load Accept Voltage — The generator must reach 
this voltage before issuing the “Accept load” sig-
nal.
 Number 
PARAMETER 
UNITS
 
Engine Flywheel Teeth 
Teeth
 
CT Ratio - Generator 
-
 
Generator Phase Configuration 
1 or 3
 
60 Hertz RPM 
RPM
 5 
Quiet-Test® 
RPM 
RPM
 Number  PARAMETER 
UNITS
 1  Preheat 
Time 
(S)econds
 
Start Detection RPM 
RPM
 3  Crank 
Time 
S
 
Alarm Hold-off Time 
S
 
Engine Warmup Time 
S
 
Target Frequency  
Hz
 7  Target 
Voltage 
Vrms
 8  Preheat 
Enable 
-
 
Engine Cooldown Time 
S
 
10 
Pause Between Cranks Time  S
 
11 
Number of Start Attempts 
-
 
12 
Load Accept Frequency 
HZ
 
13 
Load Accept Voltage 
Vrms
  6
General Information
H-100 Control Panel Technical Manual