Dump Enable — Indicates if extra load dump gov-
ernor compensation is desired to reduce increase 
in frequency caused by drop in load. The following 
three selections are available:
-  No Dump — No additional compensation.
- Dump — Reset governor algorithm when load 
dump detected.
-  Dump & Hold — Same as Dump, but also hold 
throttle closed until frequency back in range.
Engine Linearization — Selects engine torque 
to actuator position translation curve for Bosch 
Actuators.
0 = No conversion - torque = position
1 =  Butterfly Actuator with minimum position 
same as unpowered actuator
2 = Diesel arm with Horizontal rod
3 = Diesel arm with Vertical rod
4 =  Same as 1, but minimum position at actuator 
mechanical stop
5 =  Same as 4, but with limited position resolu-
tion of 1
6 =  Same as 4, but with added energy to accom-
modate throttles that normally operate in the 
nearly closed position at no load
Integral limit/Antiwindup — Choose whether to use 
an integral limit or an anti-windup strategy.
 
YES = integral limit
 
NO = anti-windup
Limit/windup parameter — If “Integral Limit” is 
selected, this is the maximum value the integral 
is allowed. If “Anti-Windup” is selected, this is the 
integral value above which the anti-windup algo-
rithm becomes active.
Pwm Counts per ampx10 — Number of PWM 
counts required to drive one tenth of an amp into 
a linear current driven actuator. This only applies 
to the “Linear Current” actuator type.
Desynch Offset — Offset of –0.9 to +0.9 Hertz to be 
applied to the target frequency to improve passive 
synchronizing by Automatic Transfer Switches. If 
an in-phase or synchronized transfer is required, 
use this setting to adjust the generator frequency 
to 0.1 Hz above nominal Utility frequency.
Governor (Speed Regulator) Option Chart
 NO.  PARAMETER 
UNITS
 
1  
Standby KP 
-
 
2  
Standby KI 
-
 
3  
Standby KD 
-
 4 
  QuietTest® 
KP 
-
 5 
  QuietTest® 
KI 
-
 6 
  QuietTest® 
KD 
-
 
7  
Actuator Type 
-
 
8  
Actuator Offset 
-
 
9  
Actuator Fullscale 
-
  10  
Actuator Normal Start Position 
-
  11  
Actuator QuietTest® Start Position 
-
  12  
Soft Start Time 
Seconds
  13  
Soft Start Frequency 
Hz
  14  
Diesel  
Y/N
  15  
Dump Enable 
-
  16  
Engine Linearization 
-
  17  
Integral limit/Antiwindup 
Y/N
  18  
Limit / windup parameter  
-
  19  
Pwm Counts per ampx10 
-
 20  Desynch 
Offset 
Hz
TRENDING
Just like in the PM-DCP, there are two types of trend-
ing available - Remote  and Local.
REMOTE TRENDING
GenLink performs remote trending by polling the 
controller for the selected data at the desired rate. 
Up to 8 analog channels can be monitored at a 0.3 
second rate. If a faster rate is desired, reducing the 
number of analog channels monitored will allow for a 
0.1 second rate. The polling rate can be varied from 
0.1 seconds to several hours. GenLink can save the 
data to a file and/or display it as a near real-time 
graph. The file is MS Excel compatible ( CSV format 
). Examples of things you can trend are the generator 
frequency response (in 0.1 second steps) to a block 
load or Generated power over a day.
‹
 
 
9
General Information
H-100 Control Panel Technical Manual