Where:
 
M is the calibration factor
 
A, B, C are polynomial coefficients
 
S is the scaling factor
 
Calibration  = M * 1024
 
Coefficient 3  = C
 
Coefficient 2  = B * 1024
 
Coefficient 1  = A
 
Scaling 
= S * 1024
POLY_1ST_N2:
First order polynomial with 4 coefficients and a scal-
ing factor
 X 
raw_analog
 
(A + BX + CX-1 + DX-2) * S
Where:
 
A, B, C, D are polynomial coefficients
 
S is the scaling factor
 
Coefficient 3  = D
 
Coefficient 2  = C
 
Coefficient 1  = B * 1024
 Calibration = 
A
 
Scaling 
= S * 1024
CFM_SENSOR:
First order polynomial with 4 coefficients and a scal-
ing factor
 
X = raw_analog - learned_offset
 
(A + BX + CX-1 + DX-2) * S
Where:
 
A, B, C, D are polynomial coefficients
 
S is the scaling factor
 
Coefficient 3  = D/32
 
Coefficient 2  = C
 
Coefficient 1  = B * 32768
 
Calibration 
= A * 64
 
Scaling 
= S * 1024
CURRENT:
CAL_SCALE:
Implements a scaling factor and a calibration factor
 
X = M * raw_analog
 X 
S
Where:
 
M is the calibration factor
 
S is the scaling factor
 
Calibration  = M * 1024
 
Scaling 
= S * 1024
GEN_FP_POLY:
Third order polynomial with 4 coefficients
 X 
raw_analog
 
AX3 + BX2 + CX + D
Where:
 
A, B, C, D are 16 bit floating point polynomial 
coefficients
 
Coefficient 3  = A
 
Coefficient 2  = B
 
Coefficient 1  = C
 Calibration = 
D
Amplitudes from 0.00000005961 (256 E-16) to 
1,098,437,885,952 (1023 E+15) are possible with 
this representation with at least 9 significant bits.
Appendix A
H-100 Control Panel Technical Manual